SMC Networks HRS200 Series Information Download Page 14

Design

Warning

1. This catalog shows the specifications of a single 

unit.

1)  Check the specifications of the single unit (contents of this 

catalog) and thoroughly consider the adaptability between 
the user’s system and this unit.

2)  Although the protection circuit as a single unit is installed, 

prepare a drain pan, water leakage sensor, discharge air 
facility, and emergency stop equipment, depending on the 
user’s operating condition. Also, the user is requested to 
carry out the safety design for the whole system.

2. When attempting to cool areas that are open to the 

atmosphere (tanks, pipes), plan your piping system 
accordingly.

When cooling open-air external tanks, arrange the piping so 
that there are coil pipes for cooling inside the tanks, and to 
carry back the entire flow volume of circulating fluid that is 
released.

3. Use non-corrosive material for fluid contact of circu-

lating fluid.

Using corrosive materials such as aluminum or iron for fluid 
contact parts such as piping may cause clogging or leakage in 
the circulating fluid circuit. Provide protection against corrosion 
when you use the product.

Selection

Warning

Model selection

For selecting a model of thermo-chiller, it is required to know the 
heat generation amount of the user’s equipment. Obtain the heat 
generation amount, referring to “Cooling Capacity Calculation” on 
pages 11 and 12 before selecting a model.

Handling

Warning

Thoroughly read the Operation Manual.

Read the Operation Manual completely before operation, and 
keep this manual available whenever necessary.

Operating Environment/Storage Environment

Warning

1. Do not use in the following environment as it will 

lead to a breakdown.

1)  In locations where water vapor, salt water, and oil may 

splash on the product.

2)  In locations where there are dust and particles.

3)  In locations where corrosive gases, organic solvents, 

chemical fluids, or flammable gases are present. (This 

product is not explosion proof.)

4)  In locations where the ambient temperature exceeds the 

limits as mentioned below.

During transportation/storage:  –15

°

C to 50

°

C (But as long 

as water or circulating fluid 

are not left inside the pipings)

During operation: –5

°

C to 45

°

C

∗   

When the ambient tempera-

ture or circulating fluid tem-

perature is 10

°

C or below, 

use the circulating fluid spec-

ified in "Operation at low am-

bient temperature or low cir-

culating fluid temperature".

5)  In locations where condensation may occur.

6)  In locations which receive direct sunlight or radiated heat.

7)  In locations where there is a heat source nearby and the 

ventilation is poor.

8)  In locations where temperature substantially changes.

9)  In locations where strong magnetic noise occurs.

(In locations where strong electric fields, strong magnetic 

fields and surge voltage occur.)

10)  In locations where static electricity occurs, or conditions 

which make the product discharge static electricity.

11)  In locations where high frequency occurs.

12)  In locations where damage is likely to occur due to lightning.

13)  In locations at altitude of 3000 m or higher (Except during 

storage and transportation)

  For altitude of 1000 m or higher

Because of lower air density, the heat radiation efficiencies 

of the devices in the product will be lower in the location at 

altitude of 1000 m or higher. Therefore, the maximum 

ambient temperature to use and the cooling capacity will 

lower according to the descriptions in the table below. 

Select the thermo-chiller considering the descriptions.

q

  Upper limit of ambient temperature: Use the product in ambient 

temperature of the described value or lower at each altitude.

w

  Cooling capacity coefficient: The product's cooling 

capacity will lower to one that multiplied by the 

described value at each altitude.

14)  In locations where strong impacts or vibrations occur.

15)  In locations where a massive force strong enough to 

deform the product is applied or a weight from a heavy 

object is applied.

16)  In locations where there is not sufficient space for maintenance.

17)  In locations where liquid that exceeds the conditions required 

for the degrees of protection IPX4 may splash on the product.

18)  Insects or plants may enter the unit. 

2. The product is not designed for clean room usage. It 

generates particles internally.

Altitude [m]

q

 Upper limit of ambient temperature [

°

C]

w

 Cooling capacity coefficient

Less than 1000 m

45

1.00

Less than 1500 m

42

0.85

Less than 2000 m

38

0.80

Less than 2500 m

35

0.75

Less than 3000 m

32

0.70

Be sure to read this before handling the products. For safety instructions and tempera-
ture control equipment precautions, refer to the “Handling Precautions for SMC Prod-
ucts” and the “Operation Manual” on the SMC website: https://www.smcworld.com

HRS200 

Series

Specific Product Precautions 1

13

Summary of Contents for HRS200 Series

Page 1: ...ort 1 This is a manual fluid fill port that is different from the automatic fluid fill port Fluid can be supplied manually into the tank without removing the side panel Fluid can be supplied manually...

Page 2: ...ay panel Eye bolt M12 4 places 715 556 851 1114 428 421 278 110 108 Overflow port Rc1 Automatic fluid fill port Rc1 2 Fluid level indicator Signal cable entry Hole 40 Grommet with membrane Power cable...

Page 3: ...Thermo chiller automatic fluid fill port 3 User s equipment To wastewater collection pit Fluid supply Circulating fluid return port Overflow port Tank drain port 4 5 2 2 2 2 1 1 6 Ensure that the ove...

Page 4: ...p when this function is operated o lamp Equipped with a power failure auto restart function which restarts the product automatically after stopped due to a power failure Lights up when this function i...

Page 5: ...optional accessories depending on the accessory the allowable current of 24 VDC devices will be reduced Refer to the operation manual of the optional accessories for details Item Specifications Conne...

Page 6: ...830 401 118 1538 HRS200 A 46 SW The circulating fluid temperature and pressure are displayed in SI units MPa C only If this option is not selected a product with a unit selection function will be prov...

Page 7: ...ed by user it is necessary to lift the thermo chiller by a forklift or sling work Carefully read the procedure manual included with this kit before performing the installation Part no Applicable model...

Page 8: ...ectric conductivity target 5 0 to 45 0 S cm Set range of electric conductivity hysteresis 2 0 to 10 0 S cm Operating temperature range Circulating fluid temperature 5 to 60 C Power consumption 400 mA...

Page 9: ...now Protection Hood Stainless steel snow protection hood for air cooled chiller According to the mounting direction of the snow protection hood the ventilation from the fan can be selected from four d...

Page 10: ...ment Element Parts List No Description Material Qty Note q Body PC PP 1 w Element 1 PP 1 e Extension piece Stainless steel 2 Conversion from NPT to Rc r Handle 1 When H is selected t Sealant tape PTFE...

Page 11: ...rm code 2 Operable items Operation start stop Circulating fluid temperature setting Alarm sound stop Key lock Key operation sound ON OFF Digital display brightness adjustment Alarm sound ON OFF HRS CV...

Page 12: ...0 C Circulating fluid return temperature T2 297 K 24 C Circulating fluid temperature difference iT 4 K T2 T1 Conversion factor minutes to seconds SI units 60 s min 1 Refer to the next page for the typ...

Page 13: ...1 kg L or using current unit system weight volume ratio 1 kgf L Specific heat C 4 19 x 103 J kg K or using current unit system 1 x 103 cal kgf C 2 Values for density and specific heat change slightly...

Page 14: ...ulating fluid spec ified in Operation at low am bient temperature or low cir culating fluid temperature 5 In locations where condensation may occur 6 In locations which receive direct sunlight or radi...

Page 15: ...glycol aqueous solution 15 wt 5 to 10 Ethylene glycol aqueous solution 15 wt Be sure to read this before handling the products For safety instructions and tempera ture control equipment precautions re...

Page 16: ...nd tempera ture control equipment precautions refer to the Handling Precautions for SMC Prod ucts and the Operation Manual on the SMC website https www smcworld com HRS200 Series Specific Product Prec...

Page 17: ...mS cm 100 1 to 300 1 v v Chloride ion Cl mg L 50 or less v Sulfuric acid ion SO4 2 mg L 50 or less v Acid consumption amount at pH4 8 mg L 50 or less v Total hardness mg L 70 or less v Calcium hardnes...

Page 18: ...rformed or will stop Power supply voltage is not within the rated voltage range of 10 In case the water level inside the tank is reduced abnormally Circulating fluid temperature is too high Compared t...

Page 19: ...Safety Instructions Be sure to read the Handling Precautions for SMC Products M E03 3 and Operation Manual before use...

Reviews: