Caution

Circulating Fluid

Tap Water (as a Circulating Fluid) Quality Standards

The Japan Refrigeration and Air Conditioning Industry Association
JRA GL-02-1994  “Cooling water system – Circulating type – Make-up water”

Warning

Maintenance

15.  The tank capacity is approx. 110 mL. When the 

fl uid level goes below the Low level, “ERR20” (Low 
fl uid level alarm) will be triggered.

1. Prevention of electric shocks and fire

Do not operate the switch with wet hands. Also, do not operate 
the thermo-con when water is present on its exterior surface.

2. Action in the case of error

If any error such as an abnormal sound, smoke, or bad odor 
occurs, cut off the power at once, and stop supplying and 
conveying fluid. Please contact SMC or a sales distributor to 
repair the thermo-con.

3. Regular inspection

Check the following items at least once a month. The 
inspection must be done by an operator who has sufficient 
knowledge and experience.
a) Check the displayed contents.
b)  Check the temperature, vibration level, and for abnormal 

sounds in the body of the thermo-con.

c) Check the voltage and current of the power supply system.
d)  Check the circulating fluid for leakage, contamination, and 

the presence of foreign matter. Replace the fluid when 
necessary.

e)  Check the flow condition and temperature of the radiated 

air.

1  In the case of [M

Ω

c m], it will be 0.003 to 0.01.

 

: Factors that have an effect on corrosion or scale generation

 Even if the water quality standards are met, complete prevention of corrosion 

is not guaranteed.

Item

Unit

Standard value

Influence

Corrosion

Scale

generation

Standard item

pH (at 25 

°

C)

6.0 to 8.0

Electric conductivity (25 

°

C)  [µS/cm]

100

1

 to 300

1

Chloride ion (Cl

)  

[mg/L]

50 or less

Sulfuric acid ion (SO

4

2–

)   

[mg/L]

50 or less

Acid consumption amount (at pH4.8)

[mg/L]

50 or less

Total hardness   

[mg/L]

70 or less

Calcium hardness (CaCO

3

)    [mg/L]

50 or less

Ionic state silica (SiO

2

)   

[mg/L]

30 or less

Reference item

Iron (Fe)   

[mg/L]

0.3 or less

Copper (Cu)   

[mg/L]

0.1 or less

Sulfide ion (S

2

)   

[mg/L]

Should not be detected.

Ammonium ion (NH

4

+

)   

[mg/L]

0.1 or less

Residual chlorine (Cl)   

[mg/L]

0.3 or less

Free carbon (CO

2

)

[mg/L]

4.0 or less

11.  If there is a point where fluid is released to 

atmosphere externally (tank or piping), minimise 
the piping resistance at the circulating fluid return 
side.

If the piping resistance is too large, the piping may be crushed 
or the built-in circulator tank may be deformed or cracked 
because the pressure in the piping for return will become 
negative. The built-in circulator tank is made of resin (PE). 
Therefore, the tank may be crushed if the pressure is negative. 
Special attention must be paid if the flow rate of the circulating 
fluid is high. To avoid a negative pressure of -0.02 MPa or 
below, the piping return should be as thick and short as 
possible to minimise piping resistance. It is also effective to 
restrict the flow rate of circulating fluid or remove the gasket of 
the internal tank for the release to atmosphere.

12. Fluorinated fluid falls outside of the specifications.

If it is used in the thermo-con, static electricity will be generated 
by the flow of fluid. This static electricity may be discharged to 
the board of the thermo-con, causing damage, operation 
failure, or loss of data such as set temperatures.
Also, as the specific gravity of the fluorinated fluid is 1.5 to 1.8 
times that of water, the pump will be overloaded, which also 
causes fluorinated fluid to fall outside the specifications. 
Therefore, if fluorinated fluid is to be used, please contact SMC 
and we will introduce you to other suitable products (water-
cooled type).

13.  Avoid operation with cavitation or bubbles due to low 

fluid level in the tank. This may shorten the pump life.

14.  If tap water is used, it should satisfy the quality 

standards shown below.

HEF 

Series

Specific Product Precautions

Be sure to read this before handling the products. Refer to the back cover for safety instructions. 
For temperature control equipment precautions, refer to the “Handling Precautions for SMC 
Products” and the “Operation Manual” on the SMC website: https://www.smc.eu

13

Summary of Contents for HEF Series

Page 1: ...94 s a 41 s Compared with the existing product HECR002 Time to change the circulating fluid temperature from 30 C to 20 C when the circulating fluid IN and OUT are directly connected Now only takes ab...

Page 2: ...se design Noise Level Sound level Noise level reference Sound example 20 dB Whisper The sound of leaves touching each other or the sound of snow falling 30 dB Very quiet Suburbs late at night or the s...

Page 3: ...emperature sensor and out from the circulating fluid outlet The heat dissipation air flow direction is as shown in Figure 2 Air is taken from the front of the Thermo con and discharged from the rear D...

Page 4: ...m Bumper Circulation Between Gas Generation Analyzer and JacketedVessel Application Examples Peltier type Chiller Thermo con Compact Type Air cooled HEF Series C mount lens F mount lens Microscope C m...

Page 5: ...ecifications p 6 Cooling Capacity p 7 Heating Capacity p 7 Pump Capacity Thermo con Outlet p 7 Dimensions p 8 Operation Display Panel p 9 Alarm p 9 Maintenance p 9 Option High Pressure Pump Mounted p...

Page 6: ...down to 20 C Water bath Example When cooling the object below a certain temperature in certain period of time Cooled substance total volume V 2 L Cooling time h 15 min Cooling temperature difference...

Page 7: ...4 Fluid contact material Stainless steel EPDM NBR Ceramics PPE PPS Carbon PP POM Electrical system Power supply 24 VDC 10 Power consumption 12 5 A Peak current 18 A Alarm Refer to Alarm Communication...

Page 8: ...rox 20 W For the high pressure pump Option the heating capacity increases by approx 10 W Pump Capacity Thermo con Outlet Circulating fluid Water 0 18 0 16 0 14 0 12 0 10 0 08 0 06 0 04 0 02 0 0 1 1 5...

Page 9: ...ignal input 5 SG 6 Output cutoff alarm open when alarm occurs 7 Common for output cutoff alarm 8 RUN STOP signal input 9 RS 485 BUS Power Cable Accessory Connector J42FSC 02V KX J S T Mfg Co Ltd made...

Page 10: ...be repaired at one of SMC s sites As a rule SMC will not conduct on site maintenance Alarm Alarm code Alarm description Operation status Main reason AL0 Memory error Stop There is an abnormality with...

Page 11: ...customer s piping resistance Cooling capacity is reduced by approx 20 W due to the heat generation from the pump P HEF002 A6 P High pressure pump mounted Options have to be selected when ordering the...

Page 12: ...ecifications Power supply input 100 240 VAC Single phase 50 60 Hz Max 3 9 A DC output 24 VDC Max 12 5 A Operating environment Ambient temperature 0 to 40 C Humidity 20 to 80 RH no condensation DC outp...

Page 13: ...s less than these values the thermo con will not be able to provide precise control and the repeated cooling and heating operations may cause it to fail 7 A magnet driven pump is used as the circulati...

Page 14: ...Copper Cu mg L 0 1 or less Sulfide ion S2 mg L Should not be detected Ammonium ion NH4 mg L 0 1 or less Residual chlorine Cl mg L 0 3 or less Free carbon CO2 mg L 4 0 or less 11 If there is a point w...

Page 15: ...of SMC products with production equipment for the manufacture of weapons of mass destruction WMD or any other weapon is strictly prohibited 2 The exports of SMC products or technology from one countr...

Page 16: ...c hu Ireland 353 0 14039000 www smcautomation ie sales smcautomation ie Italy 39 03990691 www smcitalia it mailbox smcitalia it Latvia 371 67817700 www smc lv info smc lv Lithuania 370 5 2308118 www s...

Reviews: