Air-Cooled Aftercooler
HAA
Series
- 9 -
6.
Installation
1)
Installation Location
(1)
The unit must be installed where maintenance and installation can be made easily.
(2)
The unit must be separated from the wall and the other machines 15 to over 20cm.
(3)
The unit must be installed in an indoor place where a lot moisture and dust are not
present and the unit is well ventilated.
When the unit is installed outdoors, it must be protected against wind and rain.
When the unit is used in a comparatively dusty location, it must be checked fairly frequently
to make sure the condenser is not clogged, and if necessary, cleaned with a brush, air gun
or cleaner, or it must be equipped with a dust prevention filter (optional) and cleaned periodically.
The unit must not be used in a place where adhesive dust (such as electrostatic coating powder
and oily dust) exists. Measure, such as mounting a dust on the cooler inlet port of this unit to
introduce air from the outside of the room, must be taken.
The room must be ventilated by means of a fan or other device to prevent the ambient temperature
from being raised by the exhaust heat.
(4) The temperature of the installation location must be held below 50°C.
Rated temperature is 32°C
.
The higher the temperature, the more will the cooling performance fall.
(5)
Avoid using the unit in such locations where atmosphere is full of corrosive gas such as sulfurous
acid gas, hydrogen sulfide gas, etc.
2)
Air Piping
(1)
When the compressed air from a compressor is cooled down, a lot of condensed water will be
generated. Do not forget to conduct drain piping at the outlet of the drain valve.
It is recommended to use an automatic drain system for savings in labor.
When using an SMC automatic drain system, Model AD402-03D-6-A (Model AD402-04D-6-A
for the Model HAA37 units), a base as shown in the following sketch, is required.
Please follow P.13 [9-3 M
ounting frame of Assembly Procedure]
when you use mounting frame
Of the option.
(2)
The drain piping, if conducted, should have an inside diameter of at least 10mm and a maximum
length of 5m. Improper piping will cause the back pressure to excessively increase at the time of
draining, resulting in unstable function of the auto drain.
(3) It is not possible to use it immediately after the compressor of reciprocating (The air temperature is
100
o
C or more).
In this case, we will recommend our
water-cooled aftercooler.
Warning
- When draining, follow the user’s own procedure to keep operators safe. (E.g. Wear
protective goggles, apron and gloves to prevent contact with the drained condensate.)
- When oils can enter the drained condensate, waste water treatment is necessary.
Follow the bylaws or rules of the local municipality.