background image

No.EX##-OMN0011-B 

 

 

 

 

 

 

 

 
 

PRODUCT NAME

 

 

SI unit for EtherCAT 

 

MODEL / Series / Product Number

 

 

EX260 Series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for EX260-SEC1

Page 1: ...No EX OMN0011 B PRODUCT NAME SI unit for EtherCAT MODEL Series Product Number EX260 Series...

Page 2: ...How to Order 7 Summary of Product elements 8 Installation and Cabling 9 Installation 9 Connecting cables 10 LED indication and Settings 13 Troubleshooting and Maintenance 19 Specifications 23 Table o...

Page 3: ...of equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectl...

Page 4: ...lacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to u...

Page 5: ...in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide a do...

Page 6: ...the specified torque Never mount a product in a location that will be used as a foothold The product may be damaged if excessive force is applied by stepping or climbing onto it Wiring Avoid repeated...

Page 7: ...e product in a place that is not exposed to vibration or impact Otherwise failure or malfunction can result Do not use the product in an environment that is exposed to temperature cycle Heat cycles ot...

Page 8: ...pe output specification 1 M12 connector 32 outputs source PNP negative common 2 M12 connector 32 outputs sink NPN positive common 3 M12 connector 16 outputs source PNP negative common 4 M12 connector...

Page 9: ...rating voltage for SI unit 1 M12 5 pin plug A coded 4 Ground terminal Functional earth M3 screw 5 Output connector Output signal interface for valve manifold 6 LED Bus status specific and SI unit spec...

Page 10: ...216 7 L2 80 96 112 128 144 160 176 L 9 10 11 12 13 14 15 16 L1 232 7 248 7 264 7 280 7 296 7 312 7 328 7 344 7 L2 192 208 224 240 256 272 288 304 mm The above table shows dimensions as an example for...

Page 11: ...Transmit Data 4 RD Receive Data BUS IN M12 4 pin socket D coded No Designation Description 1 TD Transmit Data 2 RD Receive Data 3 TD Transmit Data 4 RD Receive Data Connect the BUS IN connector to the...

Page 12: ...d valve 3 SI24 V 24 V for SI unit operation 4 SI0 V 0 V for SI unit operation 5 Unused Power supply line for solenoid valve and power supply line for SI unit operation are isolated Be sure to supply p...

Page 13: ...12 No EX OMN0011 B Ground terminal Connect the ground terminal to ground Resistance to ground should be 100 ohms or less...

Page 14: ...ctivity L A IN Green flickering 3 BUS IN side Link Activity OFF BUS OUT side No Link No Activity Green ON BUS OUT side Link No Activity L A OUT Green flickering 3 BUS OUT side Link Activity Green ON S...

Page 15: ...can be found on the SMC website URL http www smcworld com Setting using System Manager 1 Copy the XML file 1 for this unit to the following folder C TwinCAT lo EtherCAT this path is valid only when th...

Page 16: ...d and click the OK button If EX260 Series SI unit is not found in the list confirm whether the XML file of this unit is in the TwinCAT Io EtherCAT folder and start up TwinCAT System Manager again 2 1...

Page 17: ...the network and apply the power Then right click the I O Devices file and select Scan Devices 2 2 2 When the comment Scan for boxes appears click the YES Y button Once the scan is completed correctly...

Page 18: ...EX OMN0011 B Output number assignment Output data Output layout of the 32 outputs type Output layout of the 16 outputs type Example of EX260 SEC1 Example of EX260 SEC3 Bit unit Bit unit Byte unit Byt...

Page 19: ...igure a If you mount a single solenoid valve on the standard wiring manifold output number for B side valve is skipped Custom wiring for mixed mounting single solenoid valves and double solenoid valve...

Page 20: ...I unit PWR LED OFF All valves and valve LEDs are not operating Refer to fault No 1 SI unit PWR V LED OFF Group of valves not working Valves do not work but valve LEDs are operating SI unit L A IN LED...

Page 21: ...Fault Probable cause Recommended error handling Recommended action Check the condition of the upstream device Supply voltage to the upstream device Check the condition of L A IN side bus cable wiring...

Page 22: ...mended error handling Recommended action Poor connection between SI unit and valve manifold Check if there are any loose screws making the connection between the SI unit and the valve manifold Tighten...

Page 23: ...ening torque 0 6 Nm Precautions for maintenance 1 Be sure to switch off the power 2 Check there is no foreign matter inside the SI unit 3 Check there is no damage and no foreign matter stuck to the ga...

Page 24: ...s Item Specifications Current consumption of controller power supply 21 6 to 26 4 VDC 0 1 A max Current consumption in power supply voltage range Solenoid valve power supply 22 8 to 26 4 VDC 2 0 A or...

Page 25: ...ddress setting Manual setting is not required automatically set EX260 SEC1 SEC2 32 outputs Number of outputs EX260 SEC3 SEC4 16 outputs Vendor ID 00000114 hex 276 EX260 SEC1 01000001 hex 16777217 EX26...

Page 26: ...25 No EX OMN0011 B Dimensions...

Page 27: ...e other end Cable 2 m 2 Fieldbus interface connector BUS IN Fieldwireable connector PCA 1446553 Connector M12 straight EX500 AP010 S Connector M12 straight Cable 1 m EX500 AP050 S Connector M12 straig...

Page 28: ...t prior notice and any obligation on the part of the manufacturer EtherCAT is registered trademark and patented technology licensed by Beckhoff Automation GmbH Germany TwinCAT is registered trademark...