Installation & Maintenance Manual

SI unit-CANopen compatible

Type EX250-SCA1A

The unit and this manual contain essential information
to protect users and others from possible injury and property
damage and to ensure correct handling.
Please confirm that you fully understand the meaning of the
following messages (signs) before reading the text, and always
follow the instructions.
Please read the Installation & Maintenance Manual for related
apparatus and understand it before operating the actuator.

Do not disassemble, modify (including change of printed
circuit board) or repair.

An injury or failure can result.

Do not operate outside of the specification range.
Fire, malfunction or damage can result.
Please use it after confirming the specification.

Do not use the product in environments with possible-
presence of flammable, explosive or corrosion gas.
Otherwise fire, explosion or corrosion can result.
The product is not designed to be explosion proof.

.Connect wires and cables correctly.

.Do not connect wires while the power is on.

.Do not lay wires or cables with the same wiring route as a power line or

high-voltage line.

.Verify the insulation of the wiring.

.Take proper measures against noise such as a noise filter when the

product is incorporated in equipment or devices.

.Select an operation  environment according to enclosure(IP67). 

.Take sufficient shielding measures when installing the product at the

following place.

(1)A place where a noise due to static electricity etc. is generated
(2)A place of high electric field strength
(3)A place possibly exposed to radioactivity
(4)A place near power cable

.Do not use the product nearby a place where an electric surge is

generated.

.Use the product equipped with a surge absorber when a surge-

generating load such as a solenoid valve is driven directly.

.Prevent foreign matter such as remnant of wires from entering the

product.

.Do not expose the product to vibration and impact.

.Keep the specified ambient temperature range (-10 to +50

º

C

).

.Do not expose the product to heat radiation from a heat source located

nearby.

.Use a precision screw driver with small flat blade when setting rotary

switch and DIP switch.

.Perform maintenance and check at regular intervals.

.Perform a proper functional check.

.Do not use the product with chemicals such as benzine and thinner.

Specification

Safety Instructions

Do not apply voltages exceeding 250V between a lead
wire and a metal fitting.
Pay attention to perform an insulation test because it could
damage the insulation of the lead wire and cause failure.

These instructions must be followed when using the
product in an interlocking circuit:

.Provide double interlocking through another system

such as mechanical protection.

.Check the product regularly to ensure proper operation.

Otherwise malfunction can cause an accident.

These instructions must be followed when performing
maintenance work:

.Turn off the power supply 
.Stop the air supply, exhaust the residual pressure and

verify that the air is released before performing
maintenance work.

Otherwise it can cause injury.

Perform a proper functional check after completing
maintenance work. 
Stop operation when an abnormality is observed or the product is
not working properly.
Safety cannot be assured due to unexpected malfunctions.

NOTE

The direct-current power supply should be a UL authorized power
supply.
1.Limited voltage current circuit in accordance with UL508

A circuit to which power is supplied by the secondary coil of a
transformer that meets the following conditions. 

.Max. voltage(with no load): less than 30Vrms(42.4V peak)

.Max. current:(1)less than 8A(including when short circuited)

(2)limited by circuit protector (such as fuse) with the

following ratings

2.UL1310 compatible class 2 power supply unit or circuit of max.

30Vrms (42.4V peak) or less using a UL1585 compatible class 2
transformer as power supply. (Class 2 circuit)

Follow the instructions given below when handling the product.
Failure to follow instructions may damage the unit.

.Operate the product within the specified voltage range.

.Reserve a space around the unit for maintenance.

.Do not remove labels.

.Do not drop, hit or apply excessive shock to the product.

.Do not bend or apply tensile force to cables, or apply a force by placing

a heavy load on them.

General specification

Electrical and network specifications

Names and Functions of Individual Parts

Output equipment
connector

Indication and address
setting panel

Communication

connector

Ground terminal

Power supply connector

for output equipment,

SI unit and Input block

Input block connector

Body

.

Communication connector
To send and receive communication signals through CANopen line.
To receive the power supply for SI unit.

.

Power supply connector for output equipment, Input block
To supply power to the output equipment such as a solenoid

valve, and output block, Input block.

.

Output equipment connector
To connect the output equipment such as a solenoid valve and

output block.

.

Input block connector
To connect the Input block.

.

Indication and address setting panel
To provide LED's to indicate the condition of the unit, and the
setting of address and HOLD/CLEAR functions.

.

Ground terminal
To be connected to the ground.

Outline with Dimensions (in mm)

EX250-SCA1

SI

UNIT

PWR(V)

CAN

PWR

ADDRESS

1

0

EX250

BUS

PWR

64.4

72.16

74.9

63

17.5

42.5

59.8

16.5

46.5

Safety Instructions (continued)

Applicable solenoid valve series

EX250-TFL01GB

IMPORTANT MESSAGES

Read this manual and follow the instructions.
Signal words such as WARNING, CAUTION and NOTE, will be
followed by important safety information that must be reviewed
carefully.

Indicates a potentially hazardous situation
which could result in death or serious injury if
you do not follow instructions.

Indicates a potentially hazardous situation
which if not avoided, may result in minor injury
or moderate injury.

Provides you helpful information.

WARNING

CAUTION

NOTE

WARNING

CAUTION

No load voltage (V peak)

Max.current rating (A)

0 to 20 [V]

5.0

Above 20 to 30 [V]

100 / peak voltage

Item 

Specification 

Operating ambient temp.

-10 to +50

º

C

Operating ambient humidity 35 to 85% RH (No dew condensation)

Storage ambient temp.

-20 to +60

º

C

Vibration proof

10 to 57Hz  0.35mm (Constant amplitude)
57 to 150Hz  50m/s

2

(Constant acceleration) 

Impact proof

100m/s

2

(peak), 11ms x three times in each

direction ± X, Y and Z

Noise immunity

Normal mode : ±1500V  Pulse duration 1us
Common mode : ±1500V  Pulse duration 1us
Radiation : ±1000V  Pulse duration 1us

Withstand voltage

500V AC for 1min. 

Insulation resistance

500V DC min   10M ohm 

Operating environment

No corrosive gas and no dust

Weight 

About  250g

IP protection

IP67

Item

Specification 

Applicable system

CANopen CiA DS-301 V4.02 and
CiA DS-401

Power voltage
range 

Current
consumption

Power for SI unit
Current consumption

18 to 30V DC (24VDC typical.)
100mA or less

Power for Input
Block
Current
consumption

19.2 to 28.8V DC
Depending on the number of Input
Block stations and sensor
specifications. Max 1.0A or less

Power for solenoid
valve
Current consumption

22.8 to 26.4V DC
Depending on the number of
solenoid valve stations and
specifications. Max 2.0A or less

Solenoid valve
connection
spec.

Output type

P-ch MOS-FET Open drain type

Connection load

Solenoid valve with protection
circuit for 24V DC and 1.5W or less
surge voltage. (made by SMC)

Insulation type

Opto coupler type

Residual voltage

0.3V DC or less

Node-ID setting range

1 to 63  (1 to 127 at the SW mode)

Baudrate setting range
(Transmission speed)

1000k,800k,500k,250k,125k,50k,
20k,10kbps

COB-Identifier 

11bit ID(CAN2.0A)

Input /Output

32 points/32 points

Valve type

Valve Series

VQC series

VQC1000, VQC2000, VQC4000

SV series

SV1000, SV2000, SV3000