5 Setting 

5.1  Configuration 

An applicable GSD file is required to configure the SI unit in the 
PROFINET network. Please download the latest GSD file from the SMC 
website (URL:  

https://www.smcworld.com

). 

 

Product number 

GSD file 

56-EX260-SPN1-X42 

GSDML-V2.3-SMC-EX260-

∗∗∗∗∗∗∗∗

.xml 

 
Technical documentation giving detailed configuration information can 
be found on the SMC website (URL:  

https://www.smcworld.com

)). 

 

5.2  Output number assignment 

Output numbering starts at zero and refers to the solenoid position on 
the manifold. 

 

 

 

 

6 How to Order 

Refer to the operation manual on the SMC website (URL: 

https://www.smcworld.com

) for How to order information.

 

 

 

7 Outline Dimensions (mm) 

Refer to the operation manual on the SMC website (URL: 

https://www.smcworld.com

) for outline dimensions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8 LED Display 

 

 

 

 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 Maintenance 

9.1  General Maintenance 

Caution 

  Not following proper maintenance procedures could  cause the 

product to malfunction and lead to equipment damage. 

  If handled improperly, compressed air can be dangerous. 

  Maintenance of pneumatic systems should be performed only by 

qualified personnel. 

  Before performing maintenance, turn off the power supply and be 

sure to cut off the supply pressure. Confirm that the air is released to 
atmosphere. 

  After installation and maintenance, apply operating pressure and 

power to the equipment and perform appropriate functional and 
leakage tests to make sure the equipment is installed correctly. 

  If any electrical connections are disturbed during maintenance, 

ensure they are reconnected correctly and safety checks are carried 
out as required to ensure continued compliance with applicable 
national regulations. 

  Do not make any modification to the product. 

  Do not disassemble the product, unless required by installation or 

maintenance instructions 

  Stop operation if the product does not function correctly. 

 
 
 
 
 
 
 
 

10 Limitations of Use 

10.1 Limited warranty and Disclaimer/Compliance Requirements 

Refer to Handling Precautions for SMC Products. 

 

11 Product Disposal 

This  product shall not be disposed of as municipal waste. Check your 
local regulations and guidelines to dispose this product correctly, in 
order to reduce the impact on human health and the environment. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

12 Contacts 

Refer t

www.smcworld.com

 o

www.smc.eu

  for your local distributor / 

importer. 
 

 

URL

https://www.smcworld.com

 (Global)      

https://www.smc.eu

 (Europe) 

SMC Corporation, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, Japan 
Specifications are subject to change without prior notice from the manufacturer. 
© 2021

 

SMC Corporation All Rights Reserved. 

Template DKP50047-F-085M 

LED 

Status 

Description 

SF 

OFF 

Operating normally 

Red ON 

  SI unit related diagnostic error detected 

(load voltage for valve not supplied or 
outside specification. 

  Configuration data registered in master 

and the number of output points does 
not match. 

BF 

OFF 

Operating normally 

Red Flashing 

 PROFINET communication is not 

established. 

 IP address / device name duplicated. 

 Configuration data registered in master 

and the profile of the SI unit does not 
match. 

Red ON 

Both BUS IN and BUS OUT are not linked. 

L/A1 

Green ON 

BUS IN side: Link 

Green OFF 

BUS IN side: No Link 

Yellow Flashing  BUS IN side: Activity 

Yellow OFF 

BUS IN side: No Activity 

L/A2 

Green ON 

BUS OUT side: Link 

Green OFF 

BUS OUT side: No Link 

Yellow Flashing  BUS OUT side: Activity 

Yellow OFF 

BUS OUT side: No Activity 

PWR 

Green ON 

SI unit operating voltage supplied 

OFF 

SI unit operating voltage not supplied 

PWR(V) 

Green ON 

Load voltage for valves supplied. 

OFF 

Load voltage for valves not supplied or 
outside tolerance range (19 V or less). 

 