Version 6.00
Date of editing: 16.09.2022 r.
Page 2 of 10
Installation manual
KTS
INSTALLATION TECHNOLOGY
Before installing the fire dampers, make sure that there are no damage, during transport or storage, that could block
the baffle.
Check that the baffle can be opened and closed (full opening and closing position). To open fire dampers KTS-O-S use
the actuator key.
The opening and closing must proceed smoothly (not stepwise).
Do not pull by baffle to open or close fire damper, it may cause permanent damage, not covered by the warranty.
During KTS-O-S damper test, to opening use a key, mounted on housing.
Before installing, secure the fire damper, by dust and dirt, using a foil or other screening material. It can prevent
components of fire damper by damage.
Dampers to preserve of the declared resistance, insulation and smoke leakage EIS120, EIS90, EIS60, EIS30, should
be installed on wall, which was classified as EIS120, EIS90, EIS60, EIS30.
It is allowed to install KTS dampers in wall with other fire-resistance, should be remembered that fire-resistance in this
situation is resistance of lowest classified (in this regard) element in this system.
Ducts made of flammable and non-flammable materials can be connected to the damper. Ducts should be installed
that they cannot load the damper during fire. Ducts lengthening during fire can be compensated by support and knee.
ATTENTION: Distance between fire dampers or fire damper and construction elements must be compatible with
standard 1366-2:
a.
min. 200 [mm] between fire damper, which are installed in different ventilating wires,
b.
min. 75 [mm] between fire damper and construction element (wall/ceiling).