• The casing is made of galvanised steel, and joined by 
welding. 

• The housing is made   from galvanized steel. It has a 
symmetrical design that allows wall mounting regardless 
of air flow.

• The blade is made   of ceramic material resistant to high 
temperatures and abrasion.

• These dampers meet the conditions required for the 
symbol (S) to cold smoke seal. In case of fire, smoke 
poisoning is the leading cause of death.

• The airtightness to the passage of cold smoke is 
achieved through a joint between the perimeter of the 
housing and the blade. This design, together with the low 
thickness of the blade, allow to minimize the pressure 
loss.. 

• For high temperatures, the damper is equipped with an 
expanding intumescent seal, forming a paste that prevents 
the passage of hot air and smoke from one side of the 
damper to another.

• A rubber sealing ring at both ends of the casing ensures 
an airtightness between the damper and the ducts.

• The operating devices of the dampers is automatic 
shooting by means of a thermal fuse calibrated at 72 

°

C to 

activate the closure when reaches that temperature. Reset 
is manual except for motorized dampers.

• The fire dampers 

FMC-EIS-120

work as a separator 

between two sectors of fire and ensure the same fire 
resistance that the structural elements of 
compartmentalisation, which limits the risk of spreading 
of fire by interior of the building. 

• FMC-EIS-120 fire dampers are according with the 
following standards:

FMC-EIS-120 fire dampers EIS-120

EN 15650:2010

 

M A D E L

  

â

 

European Test Standard, EN 1366-2

(Fire resistance tests for service installations 

Part 2: Fire dampers)

European Classification  Standard, EN 13501-3

(Fire classification of construction products and building 

elements 

Part 3: Classification using data from fire resistance tests on 
products and elements used in building service installations: 

fire resisting ducts and fire dampers)

European Standard for CE Marking, EN 15650

(Ventilation for buildings. Fire dampers)

European Test Standard, EN 60529:1991

(Degrees of protection provided by enclosures (IP Code))

European Test Standard EN 1751

(Ventilation for buildings 

Air terminal devices 

Aerodynamic testing of dampers and valves)

International  Test Standard ISO 10294-4

(Fire resistance tests 

– Fire dampers for air distribution systems

Part 4: Test of thermal release mechanism)

Summary of Contents for FMC-EIS-120

Page 1: ...when reaches that temperature Reset is manual except for motorized dampers The fire dampers FMC EIS 120 work as a separator between two sectors of fire and ensure the same fire resistance that the str...

Page 2: ...S 500Pa Rigid wall Brick wall 110 mm Built in 0 360 EI 120 ve i o S 500Pa Rigid floor Reinforced concrete 150 mm Built in 0 360 EI 120 ho i o S 500Pa Sensing element load bearing capacity Sensing ele...

Page 3: ...n 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 125 Dn 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 1 Casing 2 Rubber sealing ring 3...

Page 4: ...rd Internal and external thermoelectrical fuse 72 C Automatic resetting Automatic closing by fuse 72 C Remote closing by interruption of power supply Manual test switch LED status fusible indicator Po...

Page 5: ...ction of wall floor Placement in wall floor Device position Wall Floor Device position 0 360 The minimum distance between fire dampers and construction elements will be 75mm The minimum distance betwe...

Page 6: ...ION SUPPORT Place the damper next the construction support indicated line which is painted on the label The arrows show the construction support direction B TEST MEASUREMENTS After placing the damper...

Page 7: ...ing Open and close the damper to check that the blade does not touch the duct SWITCHES NORMALLY CLOSED CONTACTS COM NF NO COM NF NO FC DC Closed damper signal Open damper signal CONTACT FC COM NO NF B...

Page 8: ...to European Standard series FMC EIS 120 M7F230V diam Operated by means of a servomotor at 230V M7F230 with closed switches Circular dampers made from galvanized steel and non combustible board Therma...

Page 9: ...125 0 008 76 382 150 0 0125 113 564 160 0 0146 129 646 200 0 0244 207 1034 250 0 0403 329 1645 300 0 0601 480 2398 315 0 0668 530 2651 PRESSURE DROP AND SOUND POWER LEVEL Pa Pa 20 200 2000 2 3 4 5 6...

Reviews:

Related manuals for FMC-EIS-120