Installation manual of KTS-O-(E)S type fire dampers in building barrier
Version: 3.1
REMARKS:
1.
Install the fire damper in such way, that the damper blade would be in horizontal
position.
2.
Fire damper cannot be the support for the constructing wall
3.
Ductwork cannot be the load for the fire damper, ductwork suspensions have to
provide full load capacity.
4.
Ductwork suspensions fixed to the fire damper have to be made in accordance with
the ductwork manufacturer instructions.
The KTS-O-E(S) fire dampers may be installed also in horizontal barriers, thicker than the
length of the damper body. In such case, ventilation duct would be partially inbuilt in the fire
barrier KWP built-in inside the barrier
Figure 2. Diagram of the KTS-O-E(S) fire damper inbuilt in a barrier thicker than the length of the damper body