9
2 Point Calibration: (Bottom & Top)
The display will now show:
Fill the tank to the required TANK LOW LEVEL, minimum suggested is liquid just covering the sensor. Wait
for approx. 60 seconds for the fluid to settle and press the Enter key. The
display will show “Setting Level
Please Wait”.
The display will now show:
Fill the tank to the TANK HIGH LEVEL. Wait for approx. 60 seconds for the fluid to settle and press the Enter
key. The display will show “Setting Level Please Wait”.
If no fluid is added the display will show:
For more information see “Calibration Tips & Tricks” on our web site www.smartswitch.co.nz
Tank
High Point
Low Point
The High Level
is not greater
than the Low level
Set
Low Level
Input = ??????? V
Set
High Level
Input = ??????? V