SET ZONE: 

 

Once a zone has been programmed (refer to programming on page 15) you can 
perform the following: 

 
This allows you to join any programmed zone to either the Port or Stb (FEC-6) Engine Relay 
Controller (if the vessel is single engine room then just select Port). Scroll with the Select Up 
or Down key through the programmed zones, until you find the zone required, and then press 
the Ent key to accept.  

 

REMOVE ZONE:

 

 
This removes the association of a zone that is associated with either the Port or Stb (FEC-6) 
Engine Relay Controller. NOTE: This only removes the association and NOT the zone. 

 

ENGINE STOP TIME:

 

 
This sets the time delay for Relay 4 on the FEC-6. If the solenoid on the extinguisher bottles 
is connected Relay 4 and the stop time is set for example to 30 seconds, this would give a 30 
second window for the fans and engine (connected to Relay 1 & 2) to stop before the 
extinguisher is set off. Also see page 14 for details.

 

.

 

AUTO / MANUAL: (Default = Manual) 

 

If Auto mode is selected and there is a fire in the zone that the FEC-6 is attached (e.g. Engine 
room) you will NOT be asked if you want to shut down the fans and engine the system will 
automatically do it. If manual is selected the system will ask you. See Relays page 14.

 

 

EXTINGUISHER SWITCH INPUT: 

 

The extinguisher bottle pressure switch may be connected to the Engine Room Relay 
Controller (FEC-6) see page 10 for details. This input is monitored and if the extinguisher 
bottle is empty the Master Display will display “Empty” if full it will display “OK”. 
 
Input 1, 2, 3 and 4 are all internally connected in the FEC-6 so multiple bottles may be 
connected. If multiple bottles are connected and one is empty the display will show “Empty” 
therefore all bottles will need to be inspected to locate the empty one.

 

 

Scroll down to ENGINE CONTROLLER at the Set-Up Menu and press the Ent key.    

 

Now scroll down to EXTINGUISHER INPUT and press the Ent key.     
This set-up is the same as in Step 2 page 15. 
 
Use the Select keys to scroll to the zone you want to use, select the name as in Step 3 page 
15 then press the Ent key. 

 

The display will now show: 

 

 
 
 
 
 

 
 
 

 

 
Use the Select Up or Down key to scroll between Port and Stb, (if the vessel is single engine 
room then just select Port) and press the Ent key to accept

.

 

 
Note: The end of line resistor is NOT required for this input. 
 
 

 

      SET THE ENGINE BOX 
    ASSOCATED WITH ZONE 
 
 
 
Select Eng I/O    Port 
Push MUTE to Exit

 

Push ENT to Enter 
 
 

Summary of Contents for FR-4000

Page 1: ...SMARTSWITCH FR 4000 Fire Alarm Monitor Installation Manual...

Page 2: ...ram Twin Engine Room Layout 7 Wiring Diagram for FR 100 9 Connection Diagram for FEC 6 FEC 1 10 Installation Electrical Specifications 11 Mounting Instructions 12 System Overview 13 Relay Operations 1...

Page 3: ...ne environment using proven techniques and materials which will ensure a long life at sea The FR 4000 provides features found only in expensive computer based systems on mega yachts but does so for a...

Page 4: ...is a controller which provides 4 Zone Inputs for Smoke Sensors and 1 Output Relay Each Input requires 4K7 end of line resistor for supervised line Minimum fault sense current 8mA Output Relay s o 10 A...

Page 5: ...Wiring Block Diagram FR 4000 Master Display Unit MDU Optional Sensors Sensor NOTE Sensors must have 4K7 ohm end of line resistor fitted Battery negative Battery positive Relay 1 FR 100 IOU Aux battery...

Page 6: ...xtinguisher trigger cupboard door 1k ohm 4K7 ohm Normally open switch Switch closes when door is opened FR 100 IOU End of line resistor Note Detector manufactures use different terminal designators E...

Page 7: ...factures use different terminal designators E g L1 L2 L3 OR Com In Out 4K7 Ohm end of line resistor EOL Note For HOCHIKI brand us terminals 1 2 6 L1 or In or 1 L1 or In or 1 L1 or In or 1 L or Com or...

Page 8: ...ut Unit Relay 1 Relay 2 Sensor Gas cylinder release door switch FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure switch Optional FEC 6 or FEC 1 FEC 1 Relay...

Page 9: ...FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure switch FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure swit...

Page 10: ...s Red Vdc Black GND Blue Coms White Coms Back View White Blue Black Red Power and Comms Wiring Connections FR 4000 FEC 6 Optional FEC 6 Optional 4 Core Cable Supplying Vdc GND Coms Coms Aux Battery Ma...

Page 11: ...Zone 2 Zone 3 Zone 3 Zone 4 Zone 4 Vdc GND N O Common N C Vdc Coms GND Vdc N O Common N C Coms GND Relay 2 Relay 1 Main Battery Main Battery Aux Battery Aux Battery Note Use only Zone 1 to 4 NOTE The...

Page 12: ...Com Relay 3 N C N O N O Com Com N C Relay 2 Relay 1 N O Com Relay 5 N C Com N O N C Relay 6 Com Com Input 1 Input 2 Input 3 Input 4 Input Common Links MUST be installed SmartSwitch Address FEC 6 www...

Page 13: ...wer Electrical Specifications FR 100 Supply Voltage 10 to 30 Volts DC Auto Sensing Quiescent Curent 30 mA Min fault sense current 8mA Relay 1 10 A resistive 24VDC Relay 2 10 A resistive 24VDC Electric...

Page 14: ...tighten the screws until the template tool can just slip on and off the screws ensure the tool in not too loose Drill the bottom hole to 12 mm cable hole Place the Display Unit keyholes over the two...

Page 15: ...nual mode it will ask you to press the enter key to start this process An extinguisher trigger cupboard door or doors may be connected to a Sensor Input Unit FR 100 This input is fully monitored and i...

Page 16: ...ed time has elapsed Relay 4 will activate Example If the solenoid on the extinguisher bottles is connected Relay 4 and the stop time is set to 30 seconds this would give a 30 second window for the fan...

Page 17: ...key to accept Step 3 Selecting Creating Zone Name s The display will now show Use the Select Up or Down key to scroll through the pre named zone names Once you have found the one required press the E...

Page 18: ...rogram a zone Think of it as each zone has a memory look up position and in the memory position is a name that the zone uses Rotary Switch 2 Zone Zone Choose one Zone name designation from list on rig...

Page 19: ...ds to the Zone you wish to remove Once the Input number has been selected press the Ent key to accept EXTINGUISHER DOOR If the vessel is fitted with an extinguisher cupboard holding the extinguisher t...

Page 20: ...needs to be associated with either the Port or Stb FEC 6 engine controller If there is only a FEC 1 fitted then you can choose either Port or Stb as either will work The display will now show Use the...

Page 21: ...shut down the fans and engine the system will automatically do it If manual is selected the system will ask you See Relays page 14 EXTINGUISHER SWITCH INPUT The extinguisher bottle pressure switch may...

Page 22: ...g mode The FR 4000 is now ready for use Alarms Should a Smoke Sensor detect smoke or fire the text FIRE will flash on the display The audible alarm will sound and both Relay 1 and Relay 2 in the FR 10...

Page 23: ...deterioration more severe than that resulting from a similar test on passivated AISI Type 304 stainless steel Locations requiring an exceptional degree of protection means a location exposed to weathe...

Page 24: ...design and Intellectual Property is owned by Penguin Electronics Ltd Po Box 272 Waikanae New Zealand Ph 0064 4 293 4201 Fax 0064 4 293 4201 Mobile 0064 274 919 805 Email info smartswitch co nz Web ww...

Reviews: