Model FEC 

– 6: 

 

An Engine Room Relay Controller can be fitted (model FEC-6) and any zone can be 
associated to that engine relay box. 
 
If there is a fire in a zone associated to the engine relay box - in auto mode it will 
automatically shut down fans, fuel pumps and/or any device attached to that relay box, in 
manual mode it will ask you to press the Ent key to start this process. 
 
When a fire is detected in a zone that has been associated with the engine controller (FEC-6) 
and the FR-4000 (MDU) is in 

Manual Mode

 the display will show: 

 

 

 
 
 
 
 
 

 
 

When the Ent key is pressed the following will happen on the FEC-6:  
 
Relay 1, 2, 3 and 4 will activate. 
 
Relay 2 and 3 can be delayed by adjusting the trim pot (next to the address select rotary 
switch) marked Rel 2 and Rel 3. Rel 2 adjusts the time for Relay 2 and Rel 3 adjusts the time 
for Relay 3. Turn Anti-clockwise to increase time.  
Relay 2 Min time = 0 seconds, max time = 1 minute. 
Relay 3 Min time = 0 seconds, max time = 1.5 minute 
 
Relay 4 has a delay associated to it called the Eng Stop Time, which is setup in the Controller 
Menu on the FR-4000 (MDU). When the programmed time has elapsed Relay 4 will activate. 
Example: If the solenoid on the extinguisher bottles is connected Relay 4 and the stop time is 
set to 30 seconds, this would give a 30 second window for the fans and engine (connected to 
Relay 1 & 2) to stop before the extinguisher is set off. 
 
Relay 5 & 6 are associated with the manual extinguisher trigger cupboard door. 
 
If the extinguisher trigger cupboard door is opened Relay 5 & 6 will activate. Relay 6 will stay 
activated until the door is closed, Relay 5 will deactivate when the Mute key is pressed on the 
FR-4000 (MDU). Example: Relay 6 connected to the evacuate engine room light and Relay 5 
connected to a buzzer. 

 

When a fire is detected in a zone that has been associated with the engine controller (FEC-6) 
and the FR-4000 (MDU) is in 

Auto Mode

 the above will happen automatically.

 

 
Model FEC 

– 1: 

 

The FEC-1 is a single Relay unit, which could be used instead of the FEC-6 if only 1 Relay is 
required. Example: To turn on the evacuate engine room light. 

 
Model FR-100: 

 

The FR-100 has two relays Relay 1 & Relay 2. Both Relay 1 and Relay 2 will only activate on 
Fire detection. Relay 1 will de-activate when the alarm is muted while Relay 2 will stay 
activated while Fire is displayed on the MDU.  
 
 
 
 

 

 

ENGINE ROOM FIRE 

 

PRESS ENT KEY TO 

          STOP ENGINE & FANS 
 
             PUSH ISOL TO ISOL 

Summary of Contents for FR-4000

Page 1: ...SMARTSWITCH FR 4000 Fire Alarm Monitor Installation Manual...

Page 2: ...ram Twin Engine Room Layout 7 Wiring Diagram for FR 100 9 Connection Diagram for FEC 6 FEC 1 10 Installation Electrical Specifications 11 Mounting Instructions 12 System Overview 13 Relay Operations 1...

Page 3: ...ne environment using proven techniques and materials which will ensure a long life at sea The FR 4000 provides features found only in expensive computer based systems on mega yachts but does so for a...

Page 4: ...is a controller which provides 4 Zone Inputs for Smoke Sensors and 1 Output Relay Each Input requires 4K7 end of line resistor for supervised line Minimum fault sense current 8mA Output Relay s o 10 A...

Page 5: ...Wiring Block Diagram FR 4000 Master Display Unit MDU Optional Sensors Sensor NOTE Sensors must have 4K7 ohm end of line resistor fitted Battery negative Battery positive Relay 1 FR 100 IOU Aux battery...

Page 6: ...xtinguisher trigger cupboard door 1k ohm 4K7 ohm Normally open switch Switch closes when door is opened FR 100 IOU End of line resistor Note Detector manufactures use different terminal designators E...

Page 7: ...factures use different terminal designators E g L1 L2 L3 OR Com In Out 4K7 Ohm end of line resistor EOL Note For HOCHIKI brand us terminals 1 2 6 L1 or In or 1 L1 or In or 1 L1 or In or 1 L or Com or...

Page 8: ...ut Unit Relay 1 Relay 2 Sensor Gas cylinder release door switch FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure switch Optional FEC 6 or FEC 1 FEC 1 Relay...

Page 9: ...FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure switch FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure swit...

Page 10: ...s Red Vdc Black GND Blue Coms White Coms Back View White Blue Black Red Power and Comms Wiring Connections FR 4000 FEC 6 Optional FEC 6 Optional 4 Core Cable Supplying Vdc GND Coms Coms Aux Battery Ma...

Page 11: ...Zone 2 Zone 3 Zone 3 Zone 4 Zone 4 Vdc GND N O Common N C Vdc Coms GND Vdc N O Common N C Coms GND Relay 2 Relay 1 Main Battery Main Battery Aux Battery Aux Battery Note Use only Zone 1 to 4 NOTE The...

Page 12: ...Com Relay 3 N C N O N O Com Com N C Relay 2 Relay 1 N O Com Relay 5 N C Com N O N C Relay 6 Com Com Input 1 Input 2 Input 3 Input 4 Input Common Links MUST be installed SmartSwitch Address FEC 6 www...

Page 13: ...wer Electrical Specifications FR 100 Supply Voltage 10 to 30 Volts DC Auto Sensing Quiescent Curent 30 mA Min fault sense current 8mA Relay 1 10 A resistive 24VDC Relay 2 10 A resistive 24VDC Electric...

Page 14: ...tighten the screws until the template tool can just slip on and off the screws ensure the tool in not too loose Drill the bottom hole to 12 mm cable hole Place the Display Unit keyholes over the two...

Page 15: ...nual mode it will ask you to press the enter key to start this process An extinguisher trigger cupboard door or doors may be connected to a Sensor Input Unit FR 100 This input is fully monitored and i...

Page 16: ...ed time has elapsed Relay 4 will activate Example If the solenoid on the extinguisher bottles is connected Relay 4 and the stop time is set to 30 seconds this would give a 30 second window for the fan...

Page 17: ...key to accept Step 3 Selecting Creating Zone Name s The display will now show Use the Select Up or Down key to scroll through the pre named zone names Once you have found the one required press the E...

Page 18: ...rogram a zone Think of it as each zone has a memory look up position and in the memory position is a name that the zone uses Rotary Switch 2 Zone Zone Choose one Zone name designation from list on rig...

Page 19: ...ds to the Zone you wish to remove Once the Input number has been selected press the Ent key to accept EXTINGUISHER DOOR If the vessel is fitted with an extinguisher cupboard holding the extinguisher t...

Page 20: ...needs to be associated with either the Port or Stb FEC 6 engine controller If there is only a FEC 1 fitted then you can choose either Port or Stb as either will work The display will now show Use the...

Page 21: ...shut down the fans and engine the system will automatically do it If manual is selected the system will ask you See Relays page 14 EXTINGUISHER SWITCH INPUT The extinguisher bottle pressure switch may...

Page 22: ...g mode The FR 4000 is now ready for use Alarms Should a Smoke Sensor detect smoke or fire the text FIRE will flash on the display The audible alarm will sound and both Relay 1 and Relay 2 in the FR 10...

Page 23: ...deterioration more severe than that resulting from a similar test on passivated AISI Type 304 stainless steel Locations requiring an exceptional degree of protection means a location exposed to weathe...

Page 24: ...design and Intellectual Property is owned by Penguin Electronics Ltd Po Box 272 Waikanae New Zealand Ph 0064 4 293 4201 Fax 0064 4 293 4201 Mobile 0064 274 919 805 Email info smartswitch co nz Web ww...

Reviews: