Install a user  

• Press and hold 1 until double signal. 
• Enter Manager code (double signal). 
• Enter user ID (1-9): double signal if the selected user is available. 
• Enter new user code (put the dallas key on the reader if needed) (double signal) and repeat new code 

(put the dallas key on the reader if needed) to confirm (double signal). 

• User code has been installed: try new code with door open. 

In case of any error (long signal) user code has not been installed. 
If the lock is set with dual mode a valid user code must be entered before press and hold 1. 

Enable-disable users 

 

• Press and hold 2 until double signal. 
• Enter Manager code (double signal).  
• All the users have been enabled (if previously disabled) or disabled (if previously enabled). 

Delete a user  

• Press and hold 3 until double signal.  
• Enter Manager code (double signal). 
• Enter user ID (1-9): double signal. 
• User code has been deleted. 

If the lock is set with dual mode a valid user code must be entered before press and hold 3. 

Self diagnostic  

• Press and hold 5 until double signal. 
• Press each key consecutively 1-2-3-4-5-6-7-8-9-0  
• Double signal: key properly working. 
• Long signal: damaged key. 

If no acoustig signal is emitted after pressing and holding 5, the lock is not properly connected to the 
keypad or the cable is damaged. 

Check users status  

• Press and hold 7 until double signal. 
• Enter Manager code (double signal). 
• Press  the key corresponding to user ID you want to check (1-2-3-4-5-6-7-8-9). 

• Double signal – user installed. 
• Single signal – user deleted. 
• Long signal – user not available. 

• Press 0 to exit the function. 

Time delay  

• Press and hold 9 until double signal. 
• Enter Manager code (double signal). 
• Enter time delay and open window values. 

• Example: 0205 to set 2 minutes time delay and 5 minutes open window. 

• Confirm time delay and open window values. 

• Example: 0205 to set 2 minutes time delay and 5 minutes open window. 

Important notes: 
 

Time delay accepted values: 00-99min. 

 

Open window accepted values: 01-19min. 

 

Time delay can be increased at any moment, can be decreased only during open window. 

 

To delete time delay set 0001 and confirm 0001.