SCCP10-050 Owner’s Manual  

 

 

 

 

 

4

Section 

Name 

12 Vdc 

24 Vdc 

Loads 

Minimum Load Size 

0.5 Adc

 

Maximum Output Current 

10 Adc 

Overload Time (Loads > 10Adc) 

5 min for Load > 100%,        

0.1 sec for Load > 125% 

Internal 
Protections  

Internal Protection 

Battery Reversal, PV Reversal 

Load Disconnect  (Automatic Reset) 

Low Battery, High Battery, 

Overload 

Load Disconnect  (Manual Reset) 

Overload (after 3 automatic 

resets) 

Low Battery Load Disconnect  

11.4 Vdc* 

22.8 Vdc* 

Low Battery Load Reconnect  

12.4 Vdc* 

24.8 Vdc* 

High Battery Load Disconnect 

15.0 Vdc

 

 30.0 

Vdc

 

 

Specifications

 

Section 

Name 

12 Vdc 

24 Vdc 

PV 

Controller Type 

PWM 

Wattage (maximum) 

120W 

240 W 

V

oc

  

Max 50 Vdc 

Short Circuit Current (maximum) 

10 Adc 

Battery 

Battery Type ( jumper-
selectable) 

Flooded or VRLA 

Nominal Voltage  

12 or 24 Vdc; automatically detected 

Battery Input (range) 

9 to 16 Vdc 

18 to 32 Vdc 

Standby Loss 

6.8 mAdc 

Conversion Efficiency 
(maximum) 

99% 

Charger 

Bulk and Absorption  
Voltages 
(maximum)  
for Battery Types  

 

Flooded 

VRLA   

Flooded 

VRLA  

Bulk 

14.8 

Vdc* 

14.6 

Vdc* 

29.6 

Vdc* 

29.2 Vdc*

Absorb 

14.8 

Vdc* 

14.4 

Vdc* 

29.6 

Vdc* 

28.8 Vdc*

Absorb Time 

2 hours* 

Float Voltage 

13.2 

Vdc* 

13.5 

Vdc* 

26.4 

Vdc* 

27.0 Vdc*

Charging Current (maximum) 

10 Adc* 

Temperature Compensation 
(range)  

-5 mV / °C / battery cell* 

Equalize 

NOTE:

 Enabled by removing battery jumper; loads turned off while equalizing 

NOTE*:

  Occurs every 60 days,

 

or following a low battery load disconnect 

Equalization Voltage (maximum) 

15.5 Vdc*

-- 

31.0 Vdc*

-- 

Equalization Time 

1 hour* 

 
Troubleshooting

 

Problem 

Possible Remedies (perform in order shown) 

Battery not charging 

1) Check battery connections   

2) Check PV voltage and connections 

3) Allow charger to cool 

No LED indicators with PV power available 

1) Check battery voltage

 

at 

controller terminals  

 

 

2) Check panel voltage at 

controller terminals

 

Red LED on 

1) Disconnect PV   

2) Disconnect battery  

3) Disconnect load   

4) Reconnect battery   

5) Reconnect PV    

6) Reconnect load 

Red LED flashing 

1) Disconnect loads 

2) Charge battery 

Yellow LED not on 

Charge battery 

Charging to wrong voltage 

1) Check position of battery selection jumper                               

Dimensions 

Size 

159 mm (6.3”)  x 68 mm (2.6”) x 25 mm 

(1.0”) 

Weight

 

~0.18 kg

 

Cabling 

Terminal Size(PV and 
battery) 

6 mm

2

(#10 AWG)

 

Cable Size (minimum) 

Battery 

6 mm

2

(#10 AWG) 

PV 

6 mm

2

(#10 AWG) 

NOTE:

 Larger cables should be used if battery cables exceed 3 m length 

NOTE:

  Battery cables must be twisted together during installation 

Environment 

Operating Temperature  

-40 °C to 60 °C 

Humidity  

0 to 95% RH non-condensing

 

Ingress Protection 

IP20

 

Battery Bank 

Minimum 50Ah at C/5 discharge rate 

Certifications 

CE, EN 61000-6-1,EN 61000-6-3, IEC/EN 62109-1 

Warranty 

2 years 

*Number shown is factory default setting.  