Specifications 

Section 

Name 

12 Vdc 

24 Vdc 

PV 

Controller Type 

MPPT 

Wattage (maximum) 

300 W 

600 W 

V

oc

 (range)  

NOTE

:  Will not operate above 

85 Vdc 

25 to 100 Vdc 

40 to 100 Vdc 

V

mp 

(range) 

15 to 70 Vdc 

27 to 70 Vdc 

Short Circuit Current (maximum) 

20 Adc 

Battery 

Battery Type ( jumper-selectable) 

Flooded or VRLA 

Nominal Voltage  

12 or 24 Vdc; automatically detected 

Battery Input (range) 

9 to 16 Vdc 

18 to 32 Vdc 

Standby Loss 

<3 mAdc 

Efficiency (maximum) 

97% 

Charger 

Bulk and Absorption  
Voltages (maximum)  
for Battery Types  

 

Flooded 

VRLA 

Flooded 

VRLA 

Bulk  14.8 Vdc* 

14.6 Vdc* 

29.6 Vdc* 

29.2 Vdc* 

Absorb  14.8 Vdc* 

14.4 Vdc* 

29.6 Vdc* 

28.8 Vdc* 

Absorb Time 

2 hours* 

Float Voltage 

13.2 Vdc* 

13.5 Vdc* 

26.4 Vdc* 

27.0 Vdc* 

Charging Current (maximum) 

20 Adc* (derated to 18 Adc at 60°C) 

Temperature Compensation (range)  

-5 mV / °C / battery cell* 

Thermistor 

10K NTC 

Equalize 

NOTE:  Enabled by removing battery jumper; loads turned off while equalizing 
NOTE*:  Occurs every 60 days,

 

or following a low battery load disconnect 

Equalization Voltage (maximum) 

15.5 Vdc* 

-- 

31.0 Vdc* 

-- 

Equalization Time 

1 hour* 

*Number shown is factory default setting. Consult the battery manufacturer for specific charger 
settings. Item is settable with communications interface. 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 Troubleshooting

 

 

Problem 

Possible Remedies (perform in order shown) 

Battery not charging 

1) Check battery connections   

2) Check PV voltage and connections 

3) Allow charger to cool 

No LED indicators with PV power available 

1) Check battery voltage

 at controller terminals

   

 

2) Check panel voltage 

at controller terminals

 

Red LED on 

1) Disconnect PV   

2) Disconnect battery  

3) Disconnect load   

4) Reconnect battery   

5) Reconnect PV     

6) Reconnect load 

Red LED  flashing 

1) Disconnect loads 

2) Charge battery 

Yellow LED not on 

Charge battery 

Charging to wrong voltage 

1) Check position of battery selection jumper 

2) Check installation of thermistor 

 

 

 

 

 

  

Section  

Name 

12 Vdc 

24 Vdc 

Loads 

Minimum Load Size 

0.25 Adc

 

Maximum Output Current 

20 Adc 

Internal 
Protections  

Internal Protection 

Battery Reversal, PV Reversal 

Load Disconnect (Automatic Reset)  

Low Battery, High Battery, Overload 

Load Disconnect  (Manual Reset) 

Overload (after 3 automatic resets) 

Low Battery Load Disconnect  

11.4 Vdc* 

22.8 Vdc* 

Low Battery Load Reconnect 

12.4 Vdc* 

24.8 Vdc* 

High Battery Load Disconnect 

15.0 Vdc

 

 

30.0 Vdc

 

 

 

Dimensions 

Size 

197 mm (7.8”) x 110 mm (4.3”) x 57 mm (2.2”) 

Weight

 

~ 1 kg

 

Cabling 

Terminal Size (PV and battery) 

≤ 32 mm

2

 (#4 AWG)

 

Cable Size (minimum) 

Battery 

16 mm

(#6 AWG) 

PV 

6 mm

(#10 AWG) 

NOTE:  Larger cables must be used if battery cables exceed 3 m length 
NOTE:  Battery cables must be twisted together during installation   

Battery Sense Required Size 

0.33 to 0.08 mm

(#22 to 28 AWG) 

Terminal Torque Value 

5.0 Nm (50 in-lb) 

Grounding  

Not required 

External Protection (recommended) 

Follow all local codes to select overcurrent 
protection. 

Battery 

 

≤ 40 Adc, ≥ 100 Vdc 

PV 

≤ 20 Adc, ≥ 100 Vdc  

Environment 

Operating Temperature  

-40°C to 60°C (derated to 18A output from 50 

to 60°C) 

Humidity  

0 to 95% RH non-condensing

 

Ingress Protection 

IP20

 

Battery Bank 

Minimum 100 Ah at C/5 discharge rate 

Certifications 

CE, EN 61000-6-1, EN 61000-6-3, IEC/EN 62109-1 

Warranty 

2 years 

 