HPM6 Power Management Controller User Manual
Page 95 of
146
12.5
TIMER SETTING
Table 31 – Timer Settings
No.
Items
Range
Default
Description
Timer Setting
1
Start Delay
(0-3600)s
5
Time from start signal is active to
genset start.
2
Stop Delay
(0-3600)s
30
Time from start signal is deactivated
to genset stop.
3
Start Output Delay
(0-3600)s
8
Start relay output time. When it is 0,
means output constantly.
4
Stop Output Delay
(0-3600)s
5
Stop relay output time. When it is 0,
means output constantly.
5
Start Wait Delay
(0-3600)s
120
Time from start signal is active to
on-load requirement is satisfied.
If the requirement doesn’t be
satisfied but delay time is up, then
the warning alarm will be initiated.
6
Stop Wait Delay
(0-3600)s
20
After the “Wait For Stop” delay, the
genset is stopped successfully if the
voltage and frequency are 0; while
the warning alarm will be initiated if
they are not 0.
7
Load Stable Delay
(0-3600)s
5
When genset starts success and
on-load stable delay is beginning.
8
Transient Fault Delay (0-100.0)s
2.0
After the on-load stable delay, If the
voltage and frequency requirements
are not satisfied after the transient
fault delay has expired, then the
“Freq/Volt Fault” alarm will be
initiated.
9
Alarm Start Delay
(0-3600)s
1
Start delay caused by trip or
shutdown alarm.
10
Trigger Start Delay
(0-3600)s
1
Start delay caused by human
triggered (e.g. manual transfer
priority, heavy consumer request and
etc.)
11
Alarm Stop Delay
(0-3600)s
1
Stop delay caused by the trip or
shutdown alarms.
12
Trigger Stop Delay
(0-3600)s
1
Stop delay caused by human
triggered (e.g. manual transfer
priority, heavy consumer request and
etc.)