HPM6 Power Management Controller User Manual
Page 135 of
146
No.
Item
Range
Default
Description
by SG as much as possible and the
maximum load will be the setting
value. If the total load is even
greater, it will be balanced by SG
and DG.
61
Max.
Load%
of
SG
Receiving
(0-100.0)%
100.0
When the controller works in both
SG mode and load-receiving
mode, if SG on-load mode is
effective, the load must be lower
than
receiving
rated
power
percentage (the setting value)
before SG is closing.
62
DG Stop% When SG
Receiving
(0-100.0)%
50.0
When the controller works in both
SG mode and load-receiving mode,
if SG on-load is effective, when SG
on-load is greater than the setting
value of the total load, DG will start
unloading and stopping and DG will
stop soft loading.
63
Max. No. of SG & DG Sync.
(1-16)
16
When SG is synchronized, the
current limit number of on-grid DG
is higher than the setting value,
closing and grid connection of SG
is not allowed.
64
Analog Control Inactive
Action
(0-2)
0
1: Previous Power Output; 2: Fixed
Power Value Output; 2: Share
Power Output.
12.13
ENGINE SETTING
Table 43 – Engine Parameter Settings
No.
Item
Range
Default
Description
Engine Setting
1
Controller Type
(0-7)
0
0: None;
1: HMC6000S;
2: HMC6000E;
3: HMC6000A;
4: HMC6000ED;
5: HMC6000EG;
6: HMC9000S;
7: HMC9000A.
2
Engine
Controller
Action
(0-1)
0: Disable
Communication failure setting of
engine controller.
3
Auto ACK
(0-1)
0: Disable