HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 49 of 69
8.2.2
CUSTOM PERIOD OUTPUT
Defined Period output is composed by 2 parts,
period output S1
and
condition output S2
.
While
S1
and
S2
are
TRUE
synchronously,
OUTPUT
;
While
S1
or
S2
is
FALSE
,
NOT OUTPUT
.
Period output S1
, can set generator‘s one or more period output freely, can set the delayed time and
output time after enter into period.
Condition output S2
; can set as any conditions in output ports.
NOTE:
when delay time and output time both are 0 in period output S1, it is TRUE in this period.
Example
,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 ac
tive, after enter ―starts time‖ and delay 2s, this defined period output is outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
8.2.3
CUSTOM COMBINED OUTPUT
Defined combination output is composed by 3 parts, OR condition output S1 or S2 and AND condition
output S3.
S1
or
S2 is
TRUE
, while S3 is
TRUE
, Defined combination output is outputting;
S1
and
S2 are
FALSE
, or S3 is
FALSE
, Defined combination output is not outputting.
NOTE:
S1, S2, S3 can be set as any c
ontents except for ―defined combination output‖ in the output setting.
NOTE:
3 parts of defined combination output (S1, S2, S3) couldn‘t include or recursively include
themselves.
Example,
Contents of probably condition output S1: output port 1 is active;
Close when probably condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of probably condition output S2, output port 2 is active;
Close when probably condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of probably condition output S3: output port 3 is active;
Close when probably condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination output is outputting; If input port 3
inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined combination output is not
outputting.