HGM7220N/HGM7220S GENSET CONTROLLER USER MANUAL 

HGM7220N/HGM7220S Genset Controller              2019-02-28            Version 1.0              Page 20 of 60 

6.4 

TRIP ALARM 

When  controller  detects  trip  alarms,  it  will  immediately  disconnect  the  generator  close  signals  but 

genset does not stop. 

Table 8 - Trip Alarms 

No. 

Type 

Description 

Over Current 

When  controller  detects  the  genset  current  value  is  higher  than  the  set 

value and action is selected 

“Trip”, it will send trip signals. 

Reverse Power 

When  controller  detects  that  the  genset  reverse  power  value  (power  is 

negative)  exceeds  the  pre-set  value,  and  action  is  selected 

“Trip”, it will 

send trip signals. 

Over Power 

When  controller  detects  that  the  genset  power  value  (power  is  positive) 

exceeds  the  pre-set  value,  and  action  is  selected 

“Trip”, it  will  send  trip 

signals. 

Input Trip 

When  input  port  is  configured  as 

“Trip”,  and  if it  is  active,  controller  will 

send trip signals.   

Mains 

Breaker 

Fail 

HGM7220S  controller:  when  controller  detects  mains  C/O  fails,  it  shall 

issue the alarm signal.   

Gen Breaker Fail 

HGM7220S controller: when controller detects generator C/O fails, it shall 

issue the alarm signal.   

Fail to Sync 

HGM7220S controller: When controller is in auto mode, if synchronization 

signal is not detected during the synchronization time for mains/generator 

synchronization close, it shall issue a warning signal.       

Summary of Contents for HGM7220N Series

Page 1: ...HGM7220N HGM7220S SERIES GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...tart genset in manual mode Manual Set the module to manual mode Auto Set the module to auto mode C O Control breaker close and open in manual mode Set Confirm Enter menu list page Move cursor in param...

Page 3: ...alarm fast flashing 5 times per second Trip and stop alarm fast flashing 5 times per second NOTES a Status Indicators illuminate always after crank disconnection and before ETS extinguished during ot...

Page 4: ...start idle delay is initiated if configured g During start idle delay period under speed under frequency under voltage alarms are inhibited When this delay is over warming up delay starts if configure...

Page 5: ...ter after stop delay and failed to stop alarm will be eliminated automatically g When after stop delay is over genset shall enter standby status 4 4 MANUAL START STOP OPERATION a HGM7220N 7220S Press...

Page 6: ...generator close occurs In the process of generator close transfer failure is detected When the detection time is due if close fails then generator close is waited for If transfer failure warning is e...

Page 7: ...of waiting for synchronization or if synchronization fails press generator C O button to cancel synchronization and generator breaker is open Then press mains C O button to force mains on load Mains D...

Page 8: ...nd action is selected Trip it will send trip signals 3 Over Power When controller detects that the genset power value power is positive exceeds the pre set value and action is selected Trip it will se...

Page 9: ...20N HGM7220S GENSET CONTROLLER USER MANUAL HGM7220N HGM7220S Genset Controller 2019 02 28 Version 1 0 Page 21 of 60 7 WIRINGS CONNECTION HGM7220N 7220S controller back panel is as below Figure 2 Back...

Page 10: ...250VAC 2 5 mm2 13 14 Charger D 1 0mm2 Connected with charger starter s D WL terminal Please hang it up if there is not this terminal 15 Aux Output 5 8A 1 5 mm2 B is supplied by Terminal 2 rated 8A Fo...

Page 11: ...0mm2 Connected to W phase output of genset 2A fuse recommended 39 Gen N2 line Input 1 0mm2 Connected to N line output of genset 40 Mains R phase Voltage Monitoring Input 1 0mm2 Connected to R phase of...

Page 12: ...e percentage return value and delay value also can be set 9 Under Voltage 0 200 80 10 Over Frequency 0 200 Disabled The setting value is mains rated frequency percentage return value and delay value a...

Page 13: ...Server www monitoryun com 3 Server Port 0 65535 91 4 Module Password 123456 16 characters 8 2 DEFINITION CONTENT OF PROGRAMMABLE OUTPUT PORTS 1 6 Table 11 Programmable Output Ports 1 6 No Type Descri...

Page 14: ...button and genset will start After the cranking times set before controller will send signal of Start Failure then press stop to reset controller Recover the action to prevent engine from cranking suc...

Page 15: ...GM7220S GENSET CONTROLLER USER MANUAL HGM7220N HGM7220S Genset Controller 2019 02 28 Version 1 0 Page 46 of 60 13 TYPICAL APPLICATION Figure 4 HGM7220S Typical Application Figure 5 HGM7220N Typical Ap...

Page 16: ...h capacity in start and fuel output is recommend 14 INSTALLATION 14 1 SGE02 EXPANSION MODULE 14 1 1 4G ANTENNA PORT Connect 4G antenna and 4G port of SGE02 Antenna port 50 SMA USB 14 1 2 GPS ANTENNA P...

Page 17: ...ys on the controller and this means SIM is not inserted or SIM contact is not good Please refer to the following installation steps Figure 9 SIM Installation Steps 14 2 FIXING CLIPS Controller is pane...

Page 18: ...ithin 1 24 VAC effective value during the full speed 12VAC is recommended in rated speed When the speed sensor is installed let the sensor spun to contacting flywheel first then make it back 1 3 lap a...

Reviews: