HGM7220N/HGM7220S GENSET CONTROLLER USER MANUAL 

HGM7220N/HGM7220S Genset Controller              2019-02-28            Version 1.0              Page 11 of 60 

4.3 

  AUTO START/STOP OPERATION   

4.3.1.  ILLUSTRATION 

Press

and the indicator beside is illuminated, meaning genset is in Auto Start mode. 

4.3.2.  AUTO START SEQUENCE 

a)  HGM7220N/HGM7220S Start Conditions:   

Mains Enable:

 When mains is abnormal (over and under voltage, over and under frequency, loss of 

phase  and  inverse  phase),  genset  enters 

“mains  abnormal  delay”  and  LCD  displays  countdown  time. 

When mains abnormal delay is ove

r, it enters “start delay”. Or when remote start (load on) input is active, 

it enters 

“start delay”.   

Mains Disable: 

When remote start (load on) input is active, genset enters 

“start delay”. 

 

b) 

“start delay” countdown is shown on LCD. 

c)  When 

start 

delay 

is 

over, 

preheating 

relay 

outputs 

(if 

configured),  “Pre-heat                                                       

Delay 

XX s” is shown on LCD.   

d)  When preheating delay is over, fuel relay outputs for 1s. Then start relay outputs; if engine cranking 

fails during “cranking time”, the fuel relay and start relay are deactivated and enter “crank rest time” 
waiting for next crank. 

e)  If engine crank fails  within  setting  times,  controller  will initiate 

“failed to start” shutdown signal and 

“failed to start” message appears on LCD display at the same time.   

f) 

In case of successful cranking

, “safety on time” starts. During this period, low oil pressure, high water 

temperature, under speed, and charge failure alarms are disabled. As soon as 

“safety on delay” is 

over, “start idle delay” is initiated (if configured). 

g) 

During “start idle delay” period, under speed, under frequency, under voltage alarms are inhibited. 
When this delay is over, “warming up delay” starts (if configured). 

h)  In case mains is abnormal and HGM7220N remote start (on-load) input is active, w

hen “warming up 

de

lay” is over, if generator status is normal, the indicator will be illuminated; if voltage and frequency 

has reached to on-load requirements, the closing relay will be energized, generator will accept load, 

generator power indicator will be lit on, and generator will enter Normal Running status; if voltage and 

frequency are abnormal, the controller will initiate shutdown alarm (shutdown alarm will be displayed 

on LCD alarm page). 

i) 

In  case  HGM7220S  remote  start  (on-load)  input  is  active,  when 

“warming  up  delay”  is  over,  if 

generator status is normal then the generator status indicator shall be illuminated. Until genset and 

mains  satisfy  the  synchronization  conditions,  the  controller  shall  issue  close  signal  and  when  the 

controller detects the close feedback signal, it shall issue immediately the open signal, and genset is 

on-load.   

NOTE: 

when remote start (off-load) signal input is active, the auto start sequence is the same as above except 

item h), generator closing relay will not output, and genset is off-load. 

 

4.3.3.  AUTO STOP SEQUENCE

 

 

 

a) 

In case HGM7220N/7220S genset is at normal running, if mains recovers normal, genset shall enter 

mains voltage “normal delay”. As soon as mains normal status is confirmed, mains status indicator 
shall be illuminated and “stop delay” starts; Or if remote start input is not active, “stop delay” starts.   

b) 

As soon as 

“stop delay” is over, 

Summary of Contents for HGM7220N Series

Page 1: ...HGM7220N HGM7220S SERIES GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...tart genset in manual mode Manual Set the module to manual mode Auto Set the module to auto mode C O Control breaker close and open in manual mode Set Confirm Enter menu list page Move cursor in param...

Page 3: ...alarm fast flashing 5 times per second Trip and stop alarm fast flashing 5 times per second NOTES a Status Indicators illuminate always after crank disconnection and before ETS extinguished during ot...

Page 4: ...start idle delay is initiated if configured g During start idle delay period under speed under frequency under voltage alarms are inhibited When this delay is over warming up delay starts if configure...

Page 5: ...ter after stop delay and failed to stop alarm will be eliminated automatically g When after stop delay is over genset shall enter standby status 4 4 MANUAL START STOP OPERATION a HGM7220N 7220S Press...

Page 6: ...generator close occurs In the process of generator close transfer failure is detected When the detection time is due if close fails then generator close is waited for If transfer failure warning is e...

Page 7: ...of waiting for synchronization or if synchronization fails press generator C O button to cancel synchronization and generator breaker is open Then press mains C O button to force mains on load Mains D...

Page 8: ...nd action is selected Trip it will send trip signals 3 Over Power When controller detects that the genset power value power is positive exceeds the pre set value and action is selected Trip it will se...

Page 9: ...20N HGM7220S GENSET CONTROLLER USER MANUAL HGM7220N HGM7220S Genset Controller 2019 02 28 Version 1 0 Page 21 of 60 7 WIRINGS CONNECTION HGM7220N 7220S controller back panel is as below Figure 2 Back...

Page 10: ...250VAC 2 5 mm2 13 14 Charger D 1 0mm2 Connected with charger starter s D WL terminal Please hang it up if there is not this terminal 15 Aux Output 5 8A 1 5 mm2 B is supplied by Terminal 2 rated 8A Fo...

Page 11: ...0mm2 Connected to W phase output of genset 2A fuse recommended 39 Gen N2 line Input 1 0mm2 Connected to N line output of genset 40 Mains R phase Voltage Monitoring Input 1 0mm2 Connected to R phase of...

Page 12: ...e percentage return value and delay value also can be set 9 Under Voltage 0 200 80 10 Over Frequency 0 200 Disabled The setting value is mains rated frequency percentage return value and delay value a...

Page 13: ...Server www monitoryun com 3 Server Port 0 65535 91 4 Module Password 123456 16 characters 8 2 DEFINITION CONTENT OF PROGRAMMABLE OUTPUT PORTS 1 6 Table 11 Programmable Output Ports 1 6 No Type Descri...

Page 14: ...button and genset will start After the cranking times set before controller will send signal of Start Failure then press stop to reset controller Recover the action to prevent engine from cranking suc...

Page 15: ...GM7220S GENSET CONTROLLER USER MANUAL HGM7220N HGM7220S Genset Controller 2019 02 28 Version 1 0 Page 46 of 60 13 TYPICAL APPLICATION Figure 4 HGM7220S Typical Application Figure 5 HGM7220N Typical Ap...

Page 16: ...h capacity in start and fuel output is recommend 14 INSTALLATION 14 1 SGE02 EXPANSION MODULE 14 1 1 4G ANTENNA PORT Connect 4G antenna and 4G port of SGE02 Antenna port 50 SMA USB 14 1 2 GPS ANTENNA P...

Page 17: ...ys on the controller and this means SIM is not inserted or SIM contact is not good Please refer to the following installation steps Figure 9 SIM Installation Steps 14 2 FIXING CLIPS Controller is pane...

Page 18: ...ithin 1 24 VAC effective value during the full speed 12VAC is recommended in rated speed When the speed sensor is installed let the sensor spun to contacting flywheel first then make it back 1 3 lap a...

Reviews: