HGM6100NC-RM Remote Monitoring Module User Manual                                              Page 13 of 14 

7

 

INSTALLATION 

7.1

 

FIXING CLIPS 

 

Controller design is panel installation method, and it is fixed by clips.     

 

Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position. 

 

Pull the fixing clip backwards (towards the back of the module) ensuring four clips are inside 
their allotted slots.   

 

Turn the fixing clip screws clockwise until they are fixed on controller panel.   

 

Care should be taken not to over tighten the screws of fixing clips. 

7.2

 

OVERALL DIMENSION AND PANEL CUTOUT 

Unit:  mm 

 

Fig. 5 Case Dimensions and Cutout 

HGM6100NC-RM  controller  can  be  applicable  for  DC  (8~35)V  battery  voltage  environment. 
Battery  negative  must  be  reliably  connected  to  engine  shell.  The  connection  wire  between 
controller power B+ and B-, and battery negative and positive should not be less than 2.5mm

2

. If a 

floating  charger  is  fitted,  please  connect  output  line  of  the  charger  with  battery  negative  and 
positive  directly,  and  then  connect  battery  positive  and  negative  to  power  input  of  controller 
separately, for the purpose of preventing charger disturbing the normal running of controller.     

 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for HGM6100NC-RM

Page 1: ...HGM6100NC RM REMOTE CONTROL MODULE USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Page 2: ...orm including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above Any reference to trademarked product names used within this publication is owned by their respectiv...

Page 3: ...ERFORMANCE AND CHARACTERISTICS 5 3 SPECIFICATION 6 4 OPERATION 7 4 1 KEY DESCRIPTIONS 7 4 2 CONTROLLER PANEL 8 4 3 REMOTE CONTROL MODE OPERATION 9 5 CONNECTIONS 10 6 TYPICAL APPLICATION 12 7 INSTALLATION 13 7 1 FIXING CLIPS 13 7 2 OVERALL DIMENSION AND PANEL CUTOUT 13 8 TROUBLESHOOTING 14 ...

Page 4: ... the monitoring mode realizing only monitoring not controlling or it can be changed over to remote control mode by local module transfer monitored and controlled remotely HGM6100NC RM remote monitoring module uses micro processing technique and 132x64 LCD display 8 kinds of languages are optional Simplified Chinese English Spanish Russian Portuguese Turkish Polish and French and can be changed fre...

Page 5: ...e same time they shall be stored in internal FLASH memory so that the parameters won t be lost in case of power outage All parameters can be set from the front panel but also can be adjusted by RS485 interface via PC All parameters of HGM6100NC RM must be configured as same as that of local module of HGM6100NC controller Wide power supply range 8 35 V DC accommodating to different starting battery...

Page 6: ... 3W Standby mode 2W Overall Dimensions 209 mm x 166 mm x 45mm Panel Cutout 186mm x 141mm Working Condition Temperature 25 70 ºC Humidity 20 93 RH Storage Condition Temperature 30 80 ºC Protection Level Front panel IP55 Insulation Intensity Apply AC2 2kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min Weight 0 56kg ...

Page 7: ...ode Close Open Under manual mode press it and breaker close open can be controlled NOTE It is only applicable for HGM6120NC RM Series Close Under manual mode press it and breaker close can be controlled NOTE It is only applicable for HGM6110NC RM Series Open Under manual mode press it and breaker open can be controlled NOTE It is only applicable for HGM6110 RM Series Set Confirm Press it and enter...

Page 8: ...cators Fig 2 HGM6120NC RM Front Panel Indicators NOTE Parts of Indicators Descriptions Alarm Indicator slowly flashes for warning alarms quickly flashes for shutdown alarms light off for none alarms Status Indicator Light off for standby status genset flashes once in start stop process always light on for normal running ...

Page 9: ... the 4th line of LCD displays remote mode on both remote module and local module which means remote control mode is active After remote mode is active genset mode transfer and genset start stop operations can be conducted NOTE if alarms occur in start stop process corresponding alarm information will be synchronously displayed on the LCD of HGM6100NC RM ...

Page 10: ... Terminal Connection Descriptions No Function Cable Size Description 1 DC input B 2 5mm2 Connected to negative of starter battery 2 DC input B 2 5mm2 Connected to positive of starter battery If wire length is over 30m double the wires in parallel Max 20A fuse is recommended 3 Emergency Stop 2 5mm2 NOTE HGM6100NC RM doesn t have the functions 4 Fuel 1 5mm2 5 Crank 1 5mm2 6 Aux Output 1 1 5mm2 7 Aux...

Page 11: ...IC 1 5mm2 26 ICOM 1 5mm2 27 U 1 0mm2 28 V 1 0mm2 29 W 1 0mm2 30 N2 1 0mm2 31 R 1 0mm2 32 S 1 0mm2 33 T 1 0mm2 34 N1 1 0mm2 35 RS485 SCR Impedance 120Ω shielding wire is recommended single end is ground connected 36 RS485 0 5mm2 37 RS485 0 5mm2 38 Aux Input 4 1 0mm2 NOTE HGM6100NC RM doesn t have the functions 39 Aux Input 5 1 0mm2 40 Sensor COM 1 0mm2 41 CAN SCR 0 5mm2 42 CAN L 0 5mm2 43 CAN H 0 5...

Page 12: ...HGM6100NC RM Remote Monitoring Module User Manual Page 12 of 14 6 TYPICAL APPLICATION Fig 4 HGM6100NC RM and HGM6100NC CAN Typical Application Diagram ...

Page 13: ...to over tighten the screws of fixing clips 7 2 OVERALL DIMENSION AND PANEL CUTOUT Unit mm Fig 5 Case Dimensions and Cutout HGM6100NC RM controller can be applicable for DC 8 35 V battery voltage environment Battery negative must be reliably connected to engine shell The connection wire between controller power B and B and battery negative and positive should not be less than 2 5mm2 If a floating c...

Page 14: ...Symptom Measures Controller no response with power Check starter battery Check controller wire connections Check DC fuse Abnormal communication of controller Check whether RS485 A and B are connected reversely Adding 120Ω resistance is recommended between RS485 A and B ______________________________________ ...