HGM400N Series Genset Controller User Manual Page 32 of 38
9
SENSOR SETTING
1)
When users reselect sensors, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGH (120°C resistor type), its sensor curve is SGH (120°C
resistor type); if users select the SGD (120°C resistor type), the temperature sensor curve is SGD
curve.
2)
If there is difference between standard sensor curve and chosen sensor curve, select “defined
sensor”, and then input defined sensor curve.
3)
When users input the sensor curve, X value (resistor) must be inputted from small to large,
otherwise, mistake occurs.
4)
If there is not oil pressure sensor, but there is low oil pressure alarm switch, users must set the oil
pressure sensor as “None”, otherwise, maybe low oil pressure shutdown occurs.
5)
The headmost or backmost values in the vertical coordinates can be set as the same as below.
Fig.3 Sensor Curve
Table 12 Common Pressure Unit Conversion Table
N/m
2
(Pa)
kgf/cm
2
bar
psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1