![Smartgen HGM150 User Manual Download Page 8](http://html.mh-extra.com/html/smartgen/hgm150/hgm150_user-manual_1297461008.webp)
HGM150 Generator Control Module
HGM150 Control Module ISSUE 2011-12-22 Version 1.3 Page 8 of 9
7 CASE DIMENSIONS (Panel Cutout 78 mm*66mm)
8 HGM170RE RELAY EXPANSION MODULE (Optional)
HGM170RE is modular structure which can be fixed in various guides with
compact structure, small size and easy installation.
Expansion circuits output:
1. Fuel relay 30A, output voltage B+, coil power
≤0.9W
2. Start relay 30A, output voltage B+, coil power
≤0.9W
3. Stop relay 30A, output voltage B+, coil power
≤0.9W
4. Auxiliary relay 30A, passive output, coil power
≤0.9W
Terminals Description
No.
Items
Description
Notes
1
CRANK CTRL Start relay control, connect to
ground.
HGM170RE terminals:
1: CRANK CTRL
3: FUEL CTRL
9: AUX CTRL
12: STOP CTRL
HGM150 terminal
:
3: Stop Output
4: Crank Disconnect
Output
5: Alarm Output
13: Over speed Output
These terminals can be
arbitrarily
2
CRANK OUT
Start relay output, B+ output.
3
FUEL CTRL
Fuel relay control, connect to
ground.
4
B+
battery positive
5
B+
Battery negative
6
FUEL OUT
Fuel relay output, B+ output.
7
GND
Battery negative (GND)
8
STOP OUT
Stop relay output, B+ output.
9
AUX CTRL
Auxiliary
relay
control,
connect to ground.
10 AUX OUT1
Auxiliary relay output, free