HGM150 Generator Control Module 

HGM150 Control Module          ISSUE 2011-12-22          Version 1.3            Page 6 of 9 

the  module  power.  If  over  speed  indicator

is  flashing  rapidly,  it 

means that over speed threshold can be set.

 

2)  Adjust  engine  speed  to  a  specified  over  speed  value,  press

,  all 

indicators illuminate; over speed threshold is the current rotating speed. 

The  valid  range  to  set  value  is  (51-75)  Hz.  Over  speed  can  be  set 

repeatedly by pressing

3)  During  setting  over  speed,  if  engine  speed  is  over  the  pre-setting, 

will  always  illuminate;  if  it  is  under  the  pre-setting, 

will 

rapidly illuminate. This can judge whether the over speed threshold is 

successfully set or not. 

4)  During  setting,  pressing

can  resume  the  factory  default:  114%  of 

rated frequency. 

5)  When  the  setting  is  completed,  turn  off  the  power  to  exit  the  setting 

state. 

5 TERMINALS FUNCTION 

◆ 

Terminal 1 (B-): Connected to plant battery negative (GND).   

◆ 

Terminal 2 (B+): Connected to plant battery positive. 

◆ 

Terminal 3 (ETS Output): When module detects fault, the output is enabled         

and will disconnect after 3 seconds. 

◆ 

Terminal 4 (Crank Disconnect Output): output when module detects output 

frequency more than 15Hz; disconnect when less than 15Hz.   

◆ 

Terminal 5 (Alarm Output): When module detects fault, the output is enabled 

and will disconnect after resetting the alarm or turning off the power. 

◆ 

Terminal 6 (Aux. Shutdown Input): auxiliary shutdown alarm input, connect 

to ground.   

◆ 

Terminal  7  (Alternate  Charger  WL  (D+)):  Connect  to  alternator  WL  (or  D+) 

terminal.  When  charge  failure,  annunciator  on  the  front  panel  illuminates. 

(indication only, not shutdown)   

◆ 

Terminal 8 (Low Oil Pressure Input): Low Oil Pressure Input port, connect to 

ground. The output will be enabled after 10s

’ start delay.   

◆ 

Terminal 9 (High Engine Temp Input): High water/cylinder temperature input 

port, connect to ground. The output will be enabled after 10s

’ start delay. 

◆ 

Terminal 10 (SIGNAL (+)), 12(SIGNAL (-)): Connect to AC voltage signal for 

judging crank disconnect and over speed protection. Voltage input range is 

Summary of Contents for HGM150

Page 1: ...HGM150 Genset Control Module USER MANUAL Smartgen Technology ...

Page 2: ...ng in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above Any reference to trademarked product names used within this publication is owned by their respective companies Smartgen Technology res...

Page 3: ...1 3 Page 3 of 9 CONTENTS 1 SUMMARY 4 2 PERFORMANCE AND CHARACTERISTICS 4 3 SPECIFICATION 4 4 PANEL OPERATION 5 5 TERMINALS FUNCTION 6 6 TYPICAL APPLICATION 7 7 CASE DIMENSIONS Panel Cutout 78 mm 66mm 8 8 HGM170RE RELAY EXPANSION MODULE Optional 8 9 OVERALL DEMENIONS OF HGM170RE 9 ...

Page 4: ...ure high water cylinder temperature over speed and external alarm protection With ETS output Crank disconnect output alarm output and over speed output LED displays all kinds of alarm states Crank disconnect and over speed are decided by generator voltage and over speed threshold can be set Built in dial switch to select frequency See the picture 3 SPECIFICATION Item Contents Working Voltage DC8 0...

Page 5: ...ed between controller and its panel Insulation Intensity Object among input output power Quote standard IEC688 1992 Test way AC1 5kV 1m 3mA leakage current Weight 0 2kg 4 PANEL OPERATION Lamp test press this key at least 1 second all the indicators in the panel will illuminate It will test whether the indication lights are normal or not Alarm reset when module had failure and alarm press this key ...

Page 6: ...D Terminal 2 B Connected to plant battery positive Terminal 3 ETS Output When module detects fault the output is enabled and will disconnect after 3 seconds Terminal 4 Crank Disconnect Output output when module detects output frequency more than 15Hz disconnect when less than 15Hz Terminal 5 Alarm Output When module detects fault the output is enabled and will disconnect after resetting the alarm ...

Page 7: ...uency is 50 60Hz Terminal 11 NC Not connection Terminal 13 Over Speed Output When module detects output frequency more than pre setting over speed threshold it will output and hold after 3s delay and will disconnect after resetting the alarm or turning off the power Terminal 14 NC Not connection 6 TYPICAL APPLICATION ...

Page 8: ... 9W 4 Auxiliary relay 30A passive output coil power 0 9W Terminals Description No Items Description Notes 1 CRANK CTRL Start relay control connect to ground HGM170RE terminals 1 CRANK CTRL 3 FUEL CTRL 9 AUX CTRL 12 STOP CTRL HGM150 terminal 3 Stop Output 4 Crank Disconnect Output 5 Alarm Output 13 Over speed Output These terminals can be arbitrarily 2 CRANK OUT Start relay output B output 3 FUEL C...

Page 9: ...ule ISSUE 2011 12 22 Version 1 3 Page 9 of 9 11 AUX OUT2 contact normally opens interconnected to control corresponding items 12 STOP CTRL Stop relay control connect to ground 9 OVERALL DEMENIONS OF HGM170RE Note When ordering please specify 12V or 24V ...

Reviews: