9.4 DEFINITE TIME DELAY AND INVERSE DEFINITE MINIMUM TIME SETTING
Definite Time
:
overcurrent delay is definite time delay. Different overcurrent value has corresponding
delay.
Inverse Definite Minimum Time(IDMT)
:
overcurrent delay decrease with the increase of overcurrent.
Different overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)
2
T
:
Overcurrent delay (second)
t
:
Timing multiplier ratio
IA
:
Current max. load current
(
L1/L2/L3
)
IT
:
Overcurrent setting value
Example
:
t = 36
IA = 550A
IT =500A