HAT700 SERIES ATS CONTROLLER USER MANUAL
HAT700 Series ATS Controller 2018-12-13 Version 1.5 Page 25 of 51
No.
Item
Range
Default
Description
16 NEL1 Set Value
(0-200)%
90
Off load output will active if the load power
has exceeded the set value and the delay
time has expired.
17 NEL1 Delay
(0-3600)s
5
18 NEL2 Set Value
(0-200)%
100
Off load output will active if the load power
has exceeded the set value and the delay
time has expired.
19 NEL2 Delay
(0-3600)s
1
20 NEL Return Enable
(0-1)
0
0: Disable ; 1: Enable
21 NEL Return Set Value
(0-200)%
50
NEL control will deactivated if the load
power has fallen below the set value and the
delay time has expired.
22 NEL Return Delay
(0-3600)s
5
23 NEL Nums
(1-3)
3
NEL number
24
Mains
Load
NEL
Enable
(0-1)
0
0: Disable ; 1: Enable
Digital Input
1
Digital Input 1
(0-29)
1
Forced Open
2
Active Type
(0-1)
0
0: Closed to active;
1: Open to active
3
Digital Input 2
(0-29)
8
Switch Trip Input
4
Active Type
(0-1)
0
0: Closed to active;
1: Open to active
5
Digital Input 3
(0-29)
0
Not Used
6
Active Type
(0-1)
0
0: Closed to active;
1: Open to active
7
Digital Input 4
(0-29)
0
Not Used
8
Active Type
(0-1)
0
0: Closed to active;
1: Open to active
Relay Output
1
Relay Output 1
(0-1)
0
0:Normally open;
1:Normally close
2
Contents Setting
(0-92)
49
ATS Power L1
3
Relay Output 2
(0-1)
0
0:Normally open;
1:Normally close
4
Contents Setting
(0-92)
52
ATS Power N
5
Relay Output 3
(0-1)
0
0:Normally open;
1:Normally close
6
Contents Setting
(0-92)
35
S1 Open Control
7
Relay Output 4
(0-1)
0
0:Normally open;
1:Normally close
8
Contents Setting
(0-92)
37
S2 Open Control
9
Relay Output 5
(0-1)
0
0:Normally open;
1:Normally close
10 Contents Setting
(0-92)
1
Custom Combined 1
11 Relay Output 6
(0-1)
0
0:Normally open;
1:Normally close
12 Contents Setting
(0-92)
32
Genset Start Output
13 Combined 1 Or Out 1 (0-1)
0
0:Normally open;