HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL
HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 15 of 35
9 PARAMETER CONFIGURATION
9.1
ILLUSTRATION
In the first page of the main screen, press
key to enter menu screen; select "Parameters Set" and
press Confirm key to confirm and enter parameter setting password check interface. Input correct
password and it will enter parameter main interface. If password is wrong, then it directly returns to main
interface. Default password is 01234. In parameter setting page, press longer
to directly exit from
this screen and return to main screen.
9.2
PARAMETER CONFIGURATION TABLE
Table 17 Parameter Configuration Items
No.
Item
Range
Default
Description
AC Setting
1
A Available Delay
(0-3600)s
10
The check time from A power abnormal to
normal.
2
A Unavailable Delay
(0-3600)s
5
The check time from A power normal to
abnormal.
3
B Available Delay
(0-3600)s
10
The check time from B power abnormal to
normal.
4
B Unavailable Delay
(0-3600)s
5
The check time from B power normal to
abnormal.
5
Set Master
(0-1)
0
0: A Master
1: B Master
6
System Type Set
(0-2)
0
0: A Mains B Gen
1: A Gen B Mains
2: A Mains B Mains
7
AC System
(0-3)
0
0: 3-Phase, 4-Wire
1: 3-Phase, 3-Wire
2: 2-Phase, 3-Wire
3: Single Phase, 2-Wire
Special custom is needed for 3 Phase 3 Wire.
8
Rated Voltage
(0~30000)V
220
Rated voltage value for AC system.
9 Over Volt Set
(0~1)
1
0: Disable
1: Enable
10
Over Volt Value
(0~200)%
120
Voltage upper limit; abnormal when it is over
upper limit.
11
Over Volt Return
(0~200)%
115
Voltage upper limit return value; normal when it
is lower than return value.
12
Under Volt Set
(0~1)
1
0: Disable
1: Enable
13
Under Volt Value
(0~200)%
80
Voltage lower limit; abnormal when it is lower
than this limit.