4.2
PUSH BUTTONS
Table 3 Button Description
Icons
Function
Description
Stop/On
Stop the running genset both in manual mode and in auto mode;
In alarm status, press this button to reset any shutdown alarms.
In stop mode, press this button and Up key to test if LCD icons and LED
indicators are OK.
In stop mode, press this button and Down to set backlight always on;
In stop process, re-press this button to stop generator immediately.
In parameter setting process, press this button to exit the setting quckly;
In stop status, press this button to start;
In start status, press longer for 3s and release to stop the genset;
Auto
Press this key and controller enters to Auto mode; under this mode, genset
can be controlled by remote start input signals;
Start
Press this key and genset will start;
Down/Decrease
LCD page scroll;
In parameter settings, decrease the value where
the cursor is;
Press the two keys
simultaneously to enter
parameter
settings
page;
Up/Increase
LCD page scroll;
In parameter settings, increase the value where
the cursor is;
Manual/Confirm
Confirm key for parameter settings page;
Manual key for other pages and press it to make controller in Manual mode;
This key is especially for MGC310;
Test/Confirm
Confirm key for parameter settings page;
Test key for other pages and press it to make controller commissoning;
This key is especially for MGC320;