Smartgen CMM366A-WIFI User Manual Download Page 4

                   

CMM366A-WIFI Cloud Monitoring Communication Module User Manual 

CMM366A-WIFI Cloud Monitoring Communication Module        2017-12-20      Version 1.0      Page 4 of 17

 

1  OVERVIEW 

CMM366A-WIFI

 Cloud Monitoring Communication Module is WIFI wireless network communication 

protocol switch module which can achieve genset (with SCI) connect to Internet. After logging into cloud 

server, module will receive corresponding genset controller communication protocol from cloud server. 

And module gains genset data via RS485 port, USB port, LINK port or RS232 port then send the data to 

corresponding cloud server through WIFI wireless network 

for achieving user’s real-time monitoring to 

running status and searching of running records via APP (IOS or Android) and PC terminal devices. 

CMM366A-WIFI

  module  not  only  can  achieve  genset  monitoring  but  also  can  insert  some  digital 

alarm input/output signal to achieve monitoring of generator room entrance guard, guard against theft 

and fire facilities. 

2  PERFORMANCE AND CHARACTERISTICS 

 

Connect to cloud server via WIFI wireless network, one to one monitoring; 

 

Multiple  ports  for  communication  with  genset  control  module:  RS485,  RS232,  LINK  and  USB 

(Host); can monitor great majority genset control modules of international first-class brands; 

 

Widely power supply: DC (8~35)V, can direct use genset build-in battery; 

 

With ARM-based 32-bit SCM, high integration of hardware and strong programming ability; 

 

Include with GPS locate function to achieve location information and locate genset; 

 

Take  JSON  network  data  communication  protocol,  upload  real-time  data  variation  and  take 

compression algorithm to vastly reduce network flow at the same time; 

 

Users can upload monitoring data to the server for analyzing based on the user-defined 

“history 

data upload interval

”;   

 

When alarm occurs it can upload data to server immediately; 

 

2 auxiliary digital input ports which can receive external alarm signal; 

 

1 auxiliary relay output ports which can output various of alarm signal; 

 

Perpetual calendar and clock functions; 

 

Power and multiple communication status indicators on front panel that working status is clear at a 

glance; 

 

Lamp test function; 

 

Parameter adjust function: users can adjust parameters via USB port; 

 

Take standard 

π-type 35mm guide-rail installation or screw-fixed installation that the module can 

be installed in the genset control box; 

 

Modular  design,  self  extinguishing  ABS  plastic  shell,  light  weight,  compact  structure  with  easy 

installation. 

 

 

 

 

 

Summary of Contents for CMM366A-WIFI

Page 1: ...CMM366A WIFI CLOUD MONITORING COMMUNICATION MODULE USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Page 2: ...material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned by their...

Page 3: ...ICS 4 3 SPECIFICATION 5 4 PANEL AND TERMINAL DESCRIPTION 6 4 1 PANEL INDICATOR AND BUTTONS 6 4 2 WIFI ANTENNA INTERFACE 7 4 3 RS485 7 4 4 RS232 7 4 5 LINK 8 4 6 USB HOST 8 4 7 USB DEVICE 8 4 8 TERMINAL 9 5 PROGRAMMABLE PARAMETERS 10 5 1 CONTENTS AND SCOPES OF PARAMETERS 10 5 2 PC CONFIGURATION INTERFACE 12 6 SYSTEM DIAGRAM 14 7 CASE DIMENSION AND INSTALLATION 15 8 TROUBLESHOOTING 16 9 PACKING LIST...

Page 4: ...ntrol module RS485 RS232 LINK and USB Host can monitor great majority genset control modules of international first class brands Widely power supply DC 8 35 V can direct use genset build in battery With ARM based 32 bit SCM high integration of hardware and strong programming ability Include with GPS locate function to achieve location information and locate genset Take JSON network data communicat...

Page 5: ...ly Overall Power Consumption Standby 2W Working 5W Auxiliary Input Volts free digital Input Auxiliary Output 1A DC30V Volts free output USB Host A type USB female port RS485 Isolated type RS232 General type LINK SmartGen exclusive port USB Device B type USB female port WIFI IPX Antenna Support 802 11b g n standard Case Dimensions 72 5mmx105mmx34mm Working Conditions Temperature 25 70 C Humidity 20...

Page 6: ... normal USB Red Normally Extinguish USB Host disabled Normally Light Communication fail Blink Communication normal WIFI Red Extinguish CMM366A WIFI login with server unsuccessfully Normally Light Communication fail Blink Communication normal LINK Red Normally Extinguish Disabled Normally Light Communication fail Blink Communication normal RS232 Red Normally Extinguish RS232 disabled Normally Light...

Page 7: ... Fig 2 WIFI Antenna Connection Diagram 4 3 RS485 Connect RS485 port with genset control module RS485 port to achieve genset data information If communication fails recommend adding a 120 Ω terminal resistor One end of shielding wire connects with SCR the other end hangs in the air Fig 3 RS485 Connection Diagram 4 4 RS232 Connect RS232 port with genset control module RS232 port to achieve genset da...

Page 8: ...l module LINK port to achieve genset data information Fig 6 LINK Connection Diagram 4 6 USB HOST Connect A type USB port with genset control module USB port to achieve genset data information Fig 6 USB HOST Connection Diagram 4 7 USB DEVICE All the parameters can be configured and view CMM366A WIFI ID Login password by connecting USB port with USB disk of PC software Fig 7 USB Connect PC Device ...

Page 9: ...ter battery 2 B 1 0mm2 Connected with positive of starter battery 3A fuse is recommended 3 Aux Input 1 1 0mm2 Active when connect to B 4 Aux Input 2 1 0mm2 Active when connect to B 5 Aux Output Normally Open 1 0mm2 Normally open output 1A DC30V 6 Common 1 0mm2 7 Normally Close 1 0mm2 8 RS485 B 0 5mm2 Impedance 120Ω shielding wire is recommended its single end earthed 9 RS485 A 0 5mm2 10 SCR 0 5mm2...

Page 10: ... 0 65535 32 characters 8 Password 0 65535 64 characters Gateway 1 Site Name 0 65535 20 Chinese characters letters or numbers 2 Server URL 0 65535 www monitoryun com 40 characters 3 Server Port 0 65535 91 4 Security Code 0 65535 123456 16 characters GPS 1 Location Info 0 1 0 0 Disabled 1 Manually Input 2 Longitude 180 180 0 000000 GPS location altitude information 3 Latitude 90 90 0 000000 4 Altitu...

Page 11: ...Fire alarm is uploaded to server when input is active 5 Alarm Input External alarm is uploaded to server when input is active 6 Reserved 7 Reserved 8 Reserved 9 Factory Test Mode It is only used for factory hardware port test when active Table 7 Relay Output Ports Content No Item Description 0 Not used Output port won t output when this item is selected 1 Digital Input 1 Active Output when auxilia...

Page 12: ...A WIFI Cloud Monitoring Communication Module 2017 12 20 Version 1 0 Page 12 of 17 5 2 PC CONFIGURATION INTERFACE Connecting the USB port of CMM366A WIFI communication module with PC USB port to configure the parameters Fig 8 WIFI Configuration Fig 9 Gateway Configuration ...

Page 13: ...CMM366A WIFI Cloud Monitoring Communication Module User Manual CMM366A WIFI Cloud Monitoring Communication Module 2017 12 20 Version 1 0 Page 13 of 17 Fig 10 Module Monitoring Screen ...

Page 14: ...I Cloud Monitoring Communication Module 2017 12 20 Version 1 0 Page 14 of 17 6 SYSTEM DIAGRAM One CMM366A WIFI module connects with one genset monitor module It can be connected via RS485 port LINK port RS232 port or USB port Figure 11 CMM366A WIFI System Application Diagram ...

Page 15: ...g Communication Module 2017 12 20 Version 1 0 Page 15 of 17 7 CASE DIMENSION AND INSTALLATION 2 ways for installation 35mm guide rail in box or screw M4 installation as below Fig 12 CMM366A WIFI Case Dimension Fig 13 CMM366A WIFI Guide Rail Installation Fig 14 CMM366A WIFI Screw Installation ...

Page 16: ...t or not Check Network socket indicator is light or not Check cable is normal or not RS485 Communication Abnormal Check connections Check RS485 port is enabled or not Check settings of genset ID and baud rate are correct or not Check RS485 s connections of A and B is reverse connect or not RS232 Communication Abnormal Check connections Check RS232 port is enabled or not Check settings of genset ID...

Page 17: ...I Cloud Monitoring Communication Module 2017 12 20 Version 1 0 Page 17 of 17 9 PACKING LIST Table 9 Packing List No Name Quantity Remark 1 CMM366A WIFI 1 2 Osculum type WIFI antenna 1 3 120Ωmatched resistor 2 4 Certification 1 5 User manual 1 _________________________________ ...

Reviews: