CMM366A-WIFI Cloud Monitoring Communication Module User Manual
CMM366A-WIFI Cloud Monitoring Communication Module 2017-12-20 Version 1.0 Page 11 of 17
No.
Items
Parameters
Defaults
Description
Ports Content
NOTE: Configuration of monitoring genset controller model, communication port, communication
baud rate, and communication ID need to be set on the (
www.smartgencloud.com
) platform, and
monitoring module need to reboot after all parameters been set.
Table 6
– Digital Input Ports Content
No.
Item
Description
0
Not Used
Not used.
1
Lamp Test
All the indicators are illuminated when input is active.
2
Remote Control Inhibited
Cloud start/stop control is prohibited when input is active.
3
Access Alarm Input
Access alarm is uploaded to server when input is active.
4
Fire Alarm Input
Fire alarm is uploaded to server when input is active.
5
Alarm Input
External alarm is uploaded to server when input is active.
6
Reserved
7
Reserved
8
Reserved
9
Factory Test Mode
It is only used for factory hardware port test when active.
Table 7
– Relay Output Ports Content
No.
Item
Description
0
Not used
Output port won’t output when this item is selected.
1
Digital Input 1 Active
Output when auxiliary input 1 is active.
2
Digital Input 2 Active
Output when auxiliary input 2 is active.
3
RS485
Communication
Failure
Output when RS485 communication fails.
4
Network Communication
Failure
Output when Network communication fails.
5
LINK Communication
Failure
Output when LINK communication fails.
6
RS232 Communication
Failure
Output when RS232 communication fails.
7
Common Alarm
Output when there is an alarm.
8
Remote Control Output
Send remote control commands via cloud platform with fixed
output delay 20s.
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved