Smartgen CMM366A-4G User Manual Download Page 4

                       

CMM366A-4G Cloud Monitoring Communication Module User Manual 

CMM366-4G Cloud Monitoring Communication Module          2017-12-25        Version 1.0        Page 4 of 16

 

1  OVERVIEW 

CMM366A-4G

  Cloud  Monitoring  Communication  Module  is  4G  GPRS  wireless  network 

communication protocol switch module which can  achieve genset (with SCI) connect to Internet. After 

logging into cloud server, module will receive corresponding genset controller communication protocol 

from cloud server. And the module gains genset data via RS485 port, USB port, LINK port or RS232 port. 

Then the module transmits the data to corresponding cloud server via 4G wireless network for achieving 
user’s real-time monitoring to running status and searching of running records via APP (IOS or Android) 

and pc terminal devices. 

CMM366A-4G

 module not only can achieve genset monitoring but also can insert some digital alarm 

input/output signal to achieve monitoring of generator room entrance guard, guard against theft and fire 

facilities. 

CMM366A-4G

  module,  which  has  GPS  locate  function,  can  upload  gained  longitude,  latitude  and 

elevation to corresponding cloud server. 

2  PERFORMANCE AND CHARACTERISTICS 

 

Connect to cloud server via 4G wireless network, one to one monitoring; 

 

Multiple  ports  for  communication  with  genset  control  module:  RS485,  RS232,  LINK  and  USB 

(Host); can monitor great majority genset control modules of international first-class brands; 

 

Widely power supply: DC (8~35)V, can direct use genset build-in battery; 

 

With ARM-based 32-bit SCM, high integration of hardware and strong programming ability; 

 

Include with GPS locate function to achieve gain location information and locate genset; 

 

Take  JSON  network  data  communication  protocol,  upload  real-time  data  variation  and  take 

compression algorithm to vastly reduce network flow at the same time; 

 

When alarm occurs it can upload data to server immediately; 

 

2 auxiliary digital input ports which can receive external alarm signal; 

 

1 auxiliary relay output ports which can output various of alarm signal; 

 

Power and multiple communication status indicators on front panel that working status is clear at a 

glance; 

 

Lamp test function; 

 

Parameter adjust function: users can adjust parameters via USB port; 

 

Take standard 

π-type 35mm guide-rail installation or screw-fixed installation that the module can 

be installed in the genset control box; 

 

Modular  design,  self  extinguishing  ABS  plastic  shell,  light  weight,  compact  structure  with  easy 

installation. 

 

 

 

 

 

 

 

Summary of Contents for CMM366A-4G

Page 1: ...CMM366A 4G CLOUD MONITORING COMMUNICATION MODULE USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Page 2: ...material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned by their...

Page 3: ...ECIFICATION 5 4 PANEL AND TERMINAL DESCRIPTION 6 4 1 PANEL INDICATOR AND BUTTONS 6 4 2 GPRS 7 4 3 GPS 7 4 4 SIM INSTALLATION 7 4 5 RS485 8 4 6 RS232 8 4 7 LINK 8 4 8 USB HOST 9 4 9 USB DEVICE 9 4 10 TERMINAL 10 5 PROGRAMMABLE PARAMETERS 11 5 1 CONTENTS AND SCOPES OF PARAMETERS 11 5 2 PC CONFIGURATION INTERFACE 12 6 SYSTEM DIAGRAM 14 7 CASE DIMENSION AND INSTALLATION 15 8 FAULT FINDING 16 9 PACKING...

Page 4: ...MANCE AND CHARACTERISTICS Connect to cloud server via 4G wireless network one to one monitoring Multiple ports for communication with genset control module RS485 RS232 LINK and USB Host can monitor great majority genset control modules of international first class brands Widely power supply DC 8 35 V can direct use genset build in battery With ARM based 32 bit SCM high integration of hardware and ...

Page 5: ... B is active Relay Output 1A DC30V Volts free output USB Host A type USB female port RS485 Isolated type RS232 General type LINK SmartGen exclusive port USB Device B type USB female port GPRS Port Standard SMA port female SMA port male for antenna GPS Port Standard SMA port female SMA port male for antenna active antenna Wireless Network LTE TDD LTE FDD HSPA TD SCDMA EVDO GSM GPRS EDGE Case Dimens...

Page 6: ...ht Communication fail Blink Communication normal USB Red Normally Extinguish USB Host disabled Normally Light Communication fail Blink Communication normal GPS Red Normally Extinguish GPS disabled Normally Light GPS not gained satellite signal Blink GPS gained satellite signal LINK Red Normally Extinguish Disabled Normally Light Communication fail Blink Communication normal RS232 Red Normally Exti...

Page 7: ...antenna to CMM366A 4G NOTE GPS antenna needs to be placed to open outdoors otherwise location information may not accurate or cannot be gained Antenna 50Ω SMA female active antenna Fig 2 CMM366A 4G Antenna Connection NOTE GPRS antenna and GPS antenna cannot be connected reversely 4 4 SIM INSTALLATION Insert 4G 3G or 2G SIM card CMM366A 4G will connect to servers via wireless mobile network NOTE 4G...

Page 8: ...ler RS485 port If communication is abnormal 120Ω terminal resistance is recommonded One end of shield wire hangs in the air and the other one connects with SCR Fig 4 RS485 Connection 4 6 RS232 Receive genset data information by connecting module RS232 port with Genset Controller RS232 port Fig 5 RS232 Connection 4 7 LINK Receive genset data information by connecting module LINK port with Genset Co...

Page 9: ...of 16 4 8 USB HOST Receive genset data information by connecting module A type USB port female port with Genset Controller USB port via USB cable Fig 7 USB HOST Connection 4 9 USB DEVICE All the parameters can be configured and view CMM366A 4G ID Login password by connecting USB port with USB disk of PC software Fig 8 USB Connect PC Device ...

Page 10: ...y 2 B 1 0mm2 Connected with positive of starter battery 3A fuse is recommended 3 Digital Input 1 1 0mm2 Active when connect to B 4 Digital Input 2 1 0mm2 Active when connect to B 5 Relay Output Normally Open 1 0mm2 Volt free output with 1A DC30V 6 Common 1 0mm2 7 Normally Close 1 0mm2 8 RS485 B 0 5mm2 Impedance 120Ω shielding wire is recommended its single end earthed 9 RS485 A 0 5mm2 10 RS485 SCR...

Page 11: ...GSM Enabled 0 1 1 0 Disabled 1 Enabled 2 GPRS Password Reserved 3 Message Center Reserved 4 PIN Enabled 0 1 0 0 Disabled 1 Enabled 5 APN 0 65535 40 characters Digital Input Digital Input 1 1 Setting 0 9 0 Default Not used 2 Type 0 1 0 0 Active when close 1 Active when open See Table 6 Digital Input Ports Content 3 Delay 0 20 0 0 0 Action delay Digital Input 2 1 Setting 0 9 1 Default Lamp test 2 Ty...

Page 12: ...ctory test when active Table 7 Relay Output Ports Content No Item Description 0 Not used Output port won t output when this item is selected 1 Digital Input 1 Active Output when auxiliary input 1 is active 2 Digital Input 2 Active Output when auxiliary input 2 is active 3 RS485 Comm Fail Output when RS485 communication fails 4 Network Comm Fail Output when Network communication fails 5 LINK Comm F...

Page 13: ...CMM366A 4G Cloud Monitoring Communication Module User Manual CMM366 4G Cloud Monitoring Communication Module 2017 12 25 Version 1 0 Page 13 of 16 Fig 10 Module Monitoring Interface ...

Page 14: ...MM366 4G Cloud Monitoring Communication Module 2017 12 25 Version 1 0 Page 14 of 16 6 SYSTEM DIAGRAM One CMM366A 4G module connects with one genset monitor module It can be connected via RS485 port LINK port RS232 port or USB port Fig 11 CMM366A 4G System Diagram ...

Page 15: ...ng Communication Module 2017 12 25 Version 1 0 Page 15 of 16 7 CASE DIMENSION AND INSTALLATION 2 ways for installation 35mm guide rail in box or screw M4 installation as below Fig 12 CMM366A 4G Case Dimension Fig 13 CMM366A 4G Guide Rail Installation Fig 14 CMM366A 4G Screw Installation ...

Page 16: ... placed outdoor or not RS485 Communication Abnormal Check connections Check RS485 port is enabled or not Check settings of genset ID and baud rate are correct or not Check RS485 s connections of A and B is reverse connect or not RS232 Communication Abnormal Check connections Check RS232 port is enabled or not Check settings of genset ID and baud rate are correct or not LINK Communication Abnormal ...