Smartgen BAC4812 User Manual Download Page 7

BAC4812 Battery Charger User Manual

BAC4812 Battery Charger

Version 1.0

2016-06-24

Page 7 of 8

5. SETTING
5.1. VOLTAGE REGULATION

When regulating current on the scene, it needs to disconnect battery and charger and measure charger
output voltage while measuring voltage potentiometer until suitable value.

5.2. CURRENT REGULATION

Output connects to battery. Measure charging current when charging voltage isn’t higher than 12.5V and
set suitable value by regulating current potentiometer (AMP). It also can estimate current value
according to current potentiometer scale.

6. OPERATION

1)Connect terminals IN+ and IN- to direct voltage 48V using BVR 1mm

2

multi-strand copper line.

2)C12V and 0V to battery positive and negative using BVR 1.5mm

2

multi-strand copper line.

3)Terminal 0V and -12V output regularly -12V. Max. output current: 200mA.
4)POWER

power supply indicator, illuminated when the charger is operating normally.

5)CHARGING

charging indicator, illuminated when charging current exceeds 0.5A.

6)VOLTS

charging voltage regulator potentiometer

7)AMP

charging current regulator potentiometer

8)FUSE

output fuse; rated current:5A; fuse will blow out when output connection reversed(no output

voltage). It will work normally once correct connection and replace the fuse.

9)Replacing fuse operation sequence:

a) Press inward using straight screwdriver with less strength while screw one time anticlockwise

and then take it out.

b) Place new fuse and slip into fuse holder. Press strongly inward with straight screwdriver while

screw one time clockwise.

Note:

Unsuitable operation or overexertion may make the fuse holder damaged.

Note:

1) Because there is diode and current-limiting circuit inner the charger, it can be used together with
charging generator, and there is no need to disconnect the charger when cranking.
2) During genset is running, high current will cause voltage drop in charging line, so recommend
separately connecting to battery terminal to avoid disturbance on sampling precision.

Summary of Contents for BAC4812

Page 1: ...BAC4812 BATTERY CHARGER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Page 2: ...d in any material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above Any reference to trademarked product names used within this publication is owned...

Page 3: ...ry Charger Version 1 0 2016 06 24 Page 3 of 8 CONTENT 1 OVERVIEW 4 2 PERFORMANCE AND CHARACTERISTICS 4 3 CHARGING PRINCIPLE 5 4 PARAMETERS CONFIGURATION 6 5 SETTING 7 5 1 VOLTAGE REGULATION 7 5 2 CURRENT REGULATION 7 6 OPERATION 7 7 CASE DIMENSIONS 8 ...

Page 4: ...ing voltage range small size light weight high efficiency rate 2 Automatic two stage charging process first constant current then constant voltage carried out according to storage battery charging characteristics to prevent overcharging and significantly prolong battery lifetime 3 With auxiliary voltage output port Firm voltage output 12V 4 12V output has current protective circuit for short circu...

Page 5: ...he battery terminal voltage exceeds the pre set value charging current will decrease with the rising of terminal voltage until the pre set current value is reached then Chargers automatically return to float mode As soon as charging current value falls below 0 5A and the constant voltage value is reached the battery is basically charged charging indicator will extinguish After that charging curren...

Page 6: ... 1 Main Output Rated Charging Current 3A Error 2 Aux Output Rated Voltage 12V Error 1V Aux Output Max Current 200mA Insulating Property Insulating Resistance Between input and output input and shell both are DC500V 1min RL 500MΩ Insulating Voltage Between input and output input and shell both are AC1500V 50Hz 1min l Leakage current IL 3 5mA Working Condition Working Temperature 30 55 C Storage Tem...

Page 7: ...rger is operating normally 5 CHARGING charging indicator illuminated when charging current exceeds 0 5A 6 VOLTS charging voltage regulator potentiometer 7 AMP charging current regulator potentiometer 8 FUSE output fuse rated current 5A fuse will blow out when output connection reversed no output voltage It will work normally once correct connection and replace the fuse 9 Replacing fuse operation s...