BAC1203VL Battery Charger User Manual
BAC1203VL Battery Charger Version 1.0 2019-06-20 Page 5 of 7
4.
PARAMETERS CONFIGURATION
Table 2 Technical Parameters
Items
Contents
24V
Input
Characteristics
Nominal AC Voltage
AC (16~36)V
Max. AC Current
3.5A
No-load Power Consumption <2W
AC Frequency
45Hz~65Hz
Max. Efficiency
80%
Output
Characteristics
No-load Output Voltage
13.8V, error±2%
Rated Charging Current
3.0A, error±5%
Max. Output Power
40W
Working
Condition
Working Temperature
(-30~+70)°C
Storage Temperature
(-40~+85)°C
Working Humidity
20%RH~93%RH ( No condensation)
Shape Structure
Weight
150g
Dimension
80mm×35.5mm×65mm (length*width*height)
5.
OPERATION
Figure 2 BAC1203VL MASK
Table 3 Wire Connection Description
Mark
Function
Description
1
Output Positive
Connects battery positive; over BVR 1.5mm
2
multi-strand
copper line is recommended.
2
Output Negative
Connects battery negative; over BVR 1.5mm
2
multi-strand
copper line is recommended.
3
Ground Terminal
Ground connected terminal;
4
AC Input Terminal
Terminal L, N shall connect (6-36)V; over BVR 1.5mm
2
multi-strand copper line is recommended.
5
Red Indicator
Charging Indicator
It illuminates when the charger is charging.
Green Indicator
Power Indicator
It illuminates when the charger is working.
NOTE1:
When this is applied on genset, charging current shall produce voltage drop on charging line. so it is
recommended to separately connect charging line to battery terminals to prevent affecting sensor precision of collecting
samples.