NB40F3UX – NB40S2UX – NB40LP2UX - NB40LPS2UX
REV 01 – Dec. 2019 - ENGLISH
BL/IR OUTPUT
This output becomes active when at least one of the
following conditions occurs:
•
Supply voltage too low (<10V in devices powered
at 10..15VDC and battery to be replaced in those
powered by 3.6V lithium battery).
•
Smoke capsule exhausted.
•
Devices in programming state (only models with
infrared).
If you want a "
device ready
" signal, switch the DIP SW5 to
the ON position, in this case the output will be active
(closed to the GND), when NUBI 4.0 is regularly powered,
functioning and ready to trigger smoke.
INPUTS WIRING
When the DIP Switches
1..4 are set to OFF,
NUBI inputs will
become active when
switched to GND.
With the DIP SW1 the inputs reference can be changed
from GND to +VCC (pin +12 V or +3V).
Using SW2, SW3, SW4 each input logic can be switched
from normally open to normally closed as shown the
following DIP Switches functional table.
In the event that the inputs are not driven with a clean
contact to GND,
never apply a voltage higher than
+VCC (pin +12 V or +3V)
, this would irreversibly
damage the electronic circuit.
DIP SWITCHES
DIP OFF
ON
1
Inputs active to GND
Inputs active to +VCC
2
CSI input normally open
CSI input normally closed
3
SI input normally open
SI input normally closed
4
ALL input normally open
ALL input normally closed
5
BL/IR output active low
BL/IR output active open
6
ALL output active low
ALL output active open.
(Not for internal siren use)
7
Operating mode
Test mode
8
Tamper enabled
Tamper disabled
DIAGNOSTIC LEDs
The LEDs are active in TEST mode (SW7 ON), except for
the red one which flashes during the alarm phase.
BLU
Pre-alarm. Only for devices with infrared
sensor. Flashes quickly when, with the
SI
input active, NUBI 4.0 has detected the
ALL-
IN
input or a movement from the infrared
sensor and waits for the second event.
VERDE
Flashes for 1 second to simulate the smoke
capsule trigger.
ROSSO
Warning. (test mode)
Alarm state. (operating mode)
OUTPUTS INTERNAL DIAGRAM
The picture shows the NUBI 4.0 outputs simplified internal
diagram.
PIR RANGE
The following image shows the integrated PIR range when
the device is installed at a height of 2.50 m.
FIT THE SMOKE CAPSULE
CAUTION
Before assembling the smoke
capsule, check the color of the
shock indicator.
Do not use the
capsule
if the indicator is
stained
red
.
Fit the smoke capsule in its housing as shown in the
following picture.
First place the lower part (1) and then rotate the capsule to
fit it in the support (2).