Longo programmable controller LPC-2.WT1
4 OPERATION
Pre installation setting and configuration is done during the assembly process. Users can set only
basic settings with the DIP switch.
4.1 Operational modes
Service
Service is enabled every time the wireless panel is turned on and connected through special cable to
the wireless panel, thus allowing only to qualified technician to set parameters. LPC-2.WT1 will save
the configuration parameters after service mode is exited via LPC Tester. This is done by setting
Service mode to "0" in RAM2.
Service mode is enabled for 3 sec. after power up. If service mode is not triggered using Smarteh
LPC Tester, then wireless panel will start in normal mode.
Normal
When exiting the service mode wireless panel goes into normal mode, trying to connect to the
wireless adapter LPC-2.WA1. If connection is established the LCD should display data according to
display setting. Using four push buttons users can turn on/off four lights. If the connection with the
LPC-2.WA1 could not be established, the sign “NO RFLINK” will be displayed.
LPC-2.WT1 has a light intensity sensor turning on/off the LCD, and significantly reducing the power
consumption. If the light is too low the LCD goes in off state. If light is increased or button is
pressed, the LCD goes in on state.
Error
In case of wireless panel communication fault, “NO RF LINK” sign appear on LCD.
4.2 Parameters
If parameter is set to logical "1", is considered to be active, enabled or set. If parameter has logical
value "0" is considered to be inactive, disabled, or cleared. Parameter can be feedback, command or
both. When parameter is marked as feedback it means that panel is sending information to the main
module. On the other hand, command represents request from the main module to the wireless
panel. Raw data is the digital value used in programming logic, which corresponds to the engineering
data, e.g. value in °C, value in %RH, Physical unit,... Note that raw data may be scaled to get
engineering data, e.g. raw data 10000 corresponds to 100.00 °C. Commands and feedbacks can be
set in Smarteh IDE.
Command
:
Light 4_On (Off/On)
[oLight4_On]
:
Remote on/off command for light4. This command is
enabled using
oLight4_rem
(Local/Remote) command.
Type: BOOL
Raw to engineering data:
“0” Light “OFF”
→
“1” Light “ON”
→
Light 3_On (Off/On)
[oLight3_On]
:
Remote on/off command for light3. This command is
enabled using
oLight3_rem
(Local/Remote) command.
Type: BOOL
Raw to engineering data:
“0” Light “OFF”
→
“1” Light “ON”
→
Light 2_On (Off/On)
[oLight2_On]
:
Remote on/off command for light2. This command is
4