Summary of Contents for LPC-2.P02

Page 1: ...USER MANUAL Longo programmable controller LPC 2 P02 Temperature Control panel Version 2 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 388 44 00 e mail info smarteh si www smarteh si...

Page 2: ...Longo programmable controller LPC 2 P02 Written by SMARTEH d o o Copyright 2012 SMARTEH d o o User manual Document Version 002 July 1 2012 i...

Page 3: ...ot include damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection s...

Page 4: ...grammable controller LPC 2 P02 1 DESCRIPTION 1 2 FEATURES 3 3 INSTALLATION 4 3 1 Connection scheme 4 3 2 Mounting instructions 6 3 3 Module labeling 7 4 REGULATION DIAGRAM 8 5 TECHNICAL SPECIFICATIONS...

Page 5: ...ys activated when heating or cooling is required depends on heating or cooling mode selection For example that two pipe system cooling mode is selected and room temperature is higher than temperature...

Page 6: ...e When more modules e g LPC 2 ID1 LPC 2 ID2 LPC 2 P01 or up to four LPC 2 P02 are connected to main module splitter e g SPL 2 is also required refer to the Figure 2 LPC 2 P02 module RS485 address 0 3...

Page 7: ...measurement room temperature 2 push buttons for temperature set point 18 LED bar graph for temperature set point Light intensity measurement LED intensity control Economic function Two four pipe heat...

Page 8: ...Longo programmable controller LPC 2 P02 3 INSTALLATION 3 1 Connection scheme Figure 2 Connection scheme 4...

Page 9: ...module Red LED indicates communication state On RS 485 communication fault Off RS 485 communication OK Temperature set point LED bar graph Green LEDs indicates actual temperature set point between mi...

Page 10: ...e to the provided leveled place on the wall 2 Fasten 2 screws DIN 7981 or similar 3 mm max head height 3 mm to fix LPC 2 P01 module to its place 3 Connect interconnection cable to the interconnection...

Page 11: ...code 001 version code reserved for future HW and or SW firmware upgrades 3 D C 40 08 is the date code 40 week and 08 year of production Label 2 description 1 S N P02 S9 0800000003 is the serial numbe...

Page 12: ...o programmable controller LPC 2 P02 4 REGULATION DIAGRAM Cooling Heating Speed I Speed II Speed III On Space temp C 0 0 Off Regulation dead band Temp Set point Space temp C 0 Temp Set point Space temp...

Page 13: ...connection connector type Berg M Power consumption 60 mA Temperature measurement accuracy 1 C Dimensions W x H x D 110 x 80 x 17 mm Weight 80 g Maximum altitude 2000 m Mounting position vertical Ambie...

Page 14: ...d system and regulation diagram Settings can be done and functions can be enabled or disabled through LPC Manager software Variables There are 22 bytes available for reading and writing from to P01 mo...

Page 15: ...BIT2 BIT3 Balcony door status Window switch status Enab Dis balcony door cmd Enab Dis window command VWORD16 N 4 variable range Max temperature status C Fx100 0 10000 Min temperature status C Fx100 0...

Page 16: ...setpoint C Fx100 0 10000 Min temperature setpoint C Fx100 0 10000 P regulation param 0 100 I regulation param 0 100 PI deadband parameter C Fx100 0 10000 Min light intensity param 0 100 Remote setpoin...

Page 17: ...controller LPC 2 P02 CHANGES The following table describes all the changes to the document Date V Description 1 7 2012 002 CGP General update 13 2 2009 001 The initial version issued as LPC 2 P02 mod...

Page 18: ...Longo programmable controller LPC 2 P02 NOTES 14...