Longo programmable controller LPC-2.DD4
Status:
Timer of overload protection
[OverloadTimer]
:
Timer countdown until the output is switched on
again (after output overload).
Type: UINT
Raw to engineering data:
0 overload protection is switched off
→
1 .. 200 0.1 .. 20 s
→
4.2 Dimmer type setting
Table 2: Dimmer type setting for type of load
Dimmer type setting
Oscillogram of 50 %
chopped sinus wave
Load types
Leading-edge
Inductive character loads, e.g. AC motor.
Trailing-edge
Resistive and capacitive character loads,
e.g. lights.
NOTE: When using LPC-2.DD4 to control dimmable lights, check manufacturer dimmer type
recommendation. Set LPC-2.DD4 accordingly.
NOTE: Using LPC-2.DD4 set as trailing-edge dimmer type controlling inductive load or using
LPC-2.DD4 set as leading-edge dimmer type controlling capacitive load, may result in LPC-2.DD4
module failure.
7