Page 26
Should you wish, you can have
both the temperature 0-10V
output and volt free relay used for
advanced ventilation. In the active
ventilation output options menu
settings select both relay and temp
0-10 ( option 3). This permits you
to open and damper and turn a fan
on for example if outside air is
suitable.
This function runs in parallel to any
alarm function using these same
output(s).
The advanced ventilation option is
independent of the alarm and
functions of the SMT-IAQ3. This function will not sound any audible alarm or impact the
LCD colour. The letter
“
A
”
will simply flash in the lower right corner of the LCD to show
the function is running.