Series 302 FIELDBUS FOUNDATION – Installation, Operation and Maintenance Manual
3.12
Display Configuration Using Syscon
The user must determine and set up the values described in the table below, for each selected
parameter.
This value indicates
that a default
parameter index 14
and the sub-index 2
of the transducer
block – LD302 are
set as monitoring
Index 14 represents
the LD302 transducer
block output. It is a DS-
64 type (DS-64)
variable, i.e., status –
float value. The sub-
index indicates the
item’s data structure,
for example, 1 selected
the status and 2
selected the
value.
When the parameter is
sample, i.e., not a data
structure, there is no
need to configure the
sub-index.
Figure 3.21 – Display Block Parameter Adjustments
Block Tag
Tag assigned to the function block.
Relative Index
Relative index of the specified block parameter.
Sub-Index
Logical member sub-index.
Mnemonic
Mnemonic assigned to the parameter.
Float Inc_Dec
Step to increase or decrease for a float or integer type.
Decimal Point
Number of decimal places after the mantissa.
Acces
Permission to Read and/or Write.
Alpha_Num
Select the mnemonic or value in the display when the value is
greater than 10,000.
Refresh
Flag to indicate new configuration.
Table 3.2 – Display Block Parameters
Local Adjustment can be fully configured by Syscon. The user can set the parameters to be
adjusted or monitored locally. Usually, these parameters are inputs and outputs of control
function blocks. It can also change the parameter mode and tuning.
Almost all function block parameters configured by Syscon, can be adjusted locally.
The user can select them using the following data types:
•
Integer
•
Float
•
Float
•
Mode
•
Tag (read – only)