Smappee Energy – Installation manual - English
14
•
Absolute power values are correct.
•
Three active power values are negative.
•
All Cos Fi are higher than 80 %.
This phase mapping
seems to be correct
but you need to
reverse the voltages
(see next step).
•
Three active power values are lower than the real power
consumption.
•
Three active power values are positive.
•
All Cos Fi are higher than 80 %.
E.g.
This phase mapping
seems to be incorrect.
Continue to find the
correct configuration.
•
Absolute power value is correct.
•
Three active power values are negative.
•
All Cos Fi are higher than 80 %.
This phase mapping
seems to be incorrect.
Continue to find the
correct configuration.
•
Three active power values are positive
•
Two Cos Fi are higher than 80 %.
•
One Cos Fi is lower than 80 %.
E.g.
This phase mapping
seems to be incorrect.
Continue to find the
correct configuration.
•
Three active power values are positive.
•
All three Cos Fi are higher than 80 %
E.g.
This phase mapping
seems to be correct.
This is the best
possible configuration.