Messages
SMA
Technologie AG
66
SB40TL_50TL-IEN081211
Installation Guide
90
< Inst. code invalid >
The Inst. code (personal installer password)
entered is not valid.
•
Enter a valid Inst. code.
< Grid param. locked >
The current country data set is locked.
•
Enter a valid Inst. code to change
the country data set.
< Waiting for main system >
•
The DC voltage at the DC input is not
sufficient to operate the main
computer.
•
The selected rotary switch setting is
not assigned for the country
configuration.
•
The parameters to be changed are
protected.
•
Ensure that sufficient DC voltage is
available (green LED lights or
flashes).
•
Check the setting of the rotary
switch (see section 6.4.2).
•
Enter Inst. code.
No
Cause
Remedy