The Sunny Boy 2500 is designed for operation on 230 V grids and works at grid
voltages of 198 V to 260 V at 49.8 Hz to 50.2 Hz. All settings shown below are
based on the German standard DIN VDE 0126. You are also able to use other
settings.
The Sunny Boy 2500 is equipped with an automatic 50 Hz / 60 Hz utility frequency
detection. It can therefore be connected to a 50 Hz or 60 Hz utility without any
further configuration changes. Pay attention to the local utility regulations in any
case.
Limit values for AC output
Voltage range
198 V ... 260 V
Frequency range
49.8 Hz ... 50.2 Hz
Voltage range
(without "MSD" independent
disconnection device)
180 V ... 260 V
Frequency range
(without "MSD" independent
disconnection device)
45.5 Hz ... 54.5 Hz