SMA
Technologie AG
Troubleshooting
Technical Description
SSM-TEN072310
Page 57
•
Is the SMU board equipped with the RS485 Piggy-Back?
•
Check the termination in the last SSM-C. The jumper must be mounted on one SMU
board (see section 7.4.4 "SSM-C Termination", page 29).
•
Check that the other SMU boards' jumpers are not mounted in the individual SSM-
Cs.
•
Is the bridge (7 - 9) fitted on the side of the SCC?
•
Is COM1 at the SCC equipped with an RS485 Piggy-Back?
•
Is COM1 configured correctly in the SCC?
LED 1 (green)
Overvoltage protector
Glows: overvoltage protector 1 ok
LED 2 (green)
Digital input (optional anti-
theft protection)
Glows: digital input / anti-theft protection ok
LED 3 (orange)
Data transfer
Glows: data transfer active
LED 4 (red)
Board fault
Glows: fault on the string current monitoring system's
control board