background image

6

9

Range Adjustment

The OPTIMA ETF-660 and ETF-770 Faucets are factory set to operate
when hands are placed 8 to 10 inches (203 to 254 mm) from Sensor.
This range should be satisfactory for most installations.
If range adjustment is required, refer to the following range
adjustment procedures.
TO MAKE A RANGE ADJUSTMENT
The Range Potentiometer and Dip Switches are located in Control
Module. Refer to illustration in Step 6.

Important: Range Potentiometer adjustment screw rotates only 3/4 of
a turn; DO NOT over-rotate.

Make certain that Dip Switch number 4 is in the UP position. Using
the small screwdriver provided, adjust Range Potentiometer clockwise
until green (power ON) indicator LED turns red (Faucet is now picking
up sink). Adjust Range Potentiometer back counterclockwise until red
LED returns to green. Range is now at maximum.

Cycle Faucet several times to assure that range as adjusted will not
inadvertently pick up IR reflection in lavatory. If IR reflection occurs
(green LED will flicker red), adjust Range Potentiometer
counterclockwise very slightly and again cycle Faucet.

Repeat range adjustment counterclockwise until length of range is at
bowl rim of lavatory (plus or minus 1” (25 mm)).

Time Out Adjustment
The Faucet Time Out Setting determines the maximum time the
Faucet will run upon continuous activation. This timing can be
changed to meet individual application requirements.
Refer to Table 1 or label on cover of Control Module along with the
following instructions to set the desired Time Out. The Dip Switches
used to set the Time Out are located in the Control Module.
Set the Time Out by configuring the number 1, 2 and 3 Dip Switches
as shown in Table 1.

Table 1 — Time Out Settings

Unless otherwise specified, all ETF-660/ETF-770 Faucets leave the
factory set with a 30 second Time Out.

Note: The position of Dip Switch # 4 (range enhancer setting) does
not affect Faucet Time Outs.

Push Cables into slots at the bottom of the Control Module.
Install Control Module cover using Screws provided. Refer to
illustration in Step 7.

Time Out

Dip Switch Setting

Switch #1

Switch #2

Switch #3

3 SECONDS

UP

UP

DOWN

6 SECONDS

DOWN

DOWN

UP

12 SECONDS

UP

DOWN

UP

30 SECONDS

UP

DOWN

DOWN

45 SECONDS

UP

UP

UP

1 MINUTE

DOWN

UP

UP

3 MINUTES

DOWN

DOWN

DOWN

20 MINUTES

DOWN

UP

DOWN

1. A continuous invisible beam of

infrared light is emitted from the
OPTIMA sensor

2. As the user’s hands enter the

beam’s effective range, 8 to 10
inches (203 to 254 mm), the beam
is reflected back into the sensor
receiver and activates the solenoid
valve allowing tempered water to
flow from the faucet into the sink.
Water will flow until the hands are
removed or until the faucet reaches
its automatic time out limit setting.

3. When hands are moved away from

the OPTIMA ON-Q

®

sensor, the loss

of reflected light initiates an
electrical signal that deactivates the
solenoid valve, shutting off the
water flow. The circuit then
automatically resets and is ready for
the next user.

Test Faucet Operation

CARE AND CLEANING OF CHROME
AND SPECIAL FINISHES

DO NOT use abrasive or chemical cleaners (including chlorine
bleach) to clean faucets that may dull the luster and attack the chrome
or special decorative finishes. Use ONLY soap and water, then wipe
dry with clean cloth or towel.
When cleaning the bathroom tile, protect the faucet from any
splattering of cleaner. Acids and cleaning fluids will discolor or
remove chrome plating.

Summary of Contents for ETF-660

Page 1: ...ng for each solenoid valve used Refer to Step 5 Install Transformer for further information Mixing Valve When installing the faucet with a Sloan mixing valve these Installation Instructions AND the Installation Instructions packaged with the mixing valve MUST be followed Important INSTALL ALL ELECTRICAL WIRING IN ACCORDANCE WITH NATIONAL LOCAL CODES AND REGULATIONS INSTALL ALL PLUMBING IN ACCORDAN...

Page 2: ...t with BDM and BDT Variation Mixing Valves for Hot and Cold Water Supply shown with 4 trim plate ETF 770 Faucet with Bak Chek Tee for Hot and Cold Water Supply shown with 4 trim plate ETF 770 Faucet with ADM Variation Mixing Valve for Hot and Cold Water Supply shown with 4 trim plate ETF 770 Faucet with BDM and BDT Variation Mixing Valves for Hot and Cold Water Supply shown with 4 trim plate ETF 6...

Page 3: ...LL BEVEL SIDE DOWN NUT TRIM PLATE FAUCET SHANK SPOUT TRIM PLATE OPTIONAL WASHER NUT SPOUT ETF 660 FAUCET ETF 770 FAUCET TRIM PLATE OPTIONAL WASHER NUT FAUCET SHANK RUBBER WASHER 4 Connect Supply Line s Note If installation includes a Sloan mixing valve refer to the Installation Instructions supplied with the Sloan mixing valve Flush dirt debris and sediment from the supply line s FOR DUAL LINE HOT...

Page 4: ... Faucet 18 gauge wire is recommended A Run wires from secondary side of Transformer to 3 8 inch 10 mm hole at back of Control Module Enclosure If necessary wires can be run through wall and then inserted through hole in back of Control Module Enclosure Plug in Transformers Important DO NOT plug Transformer into receptacle until all wiring has been completed The Transformer is supplied with a 10 fo...

Page 5: ...LOTS FROM FAUCET SPOUT TERMINAL BLOCK 1 REMOVE TERMINAL BLOCK 2 INSERT POWER CABLES 3 SECURE WITH SCREWS 4 REINSTALL TERMINAL BLOCK CONNECTOR BOARD POWER CABLE MODULAR RECEPTACLE B Insert Solenoid Valve Connector into the Modular Receptacle on Connector Board D Insert each Conduit Cable into a strain relief slot in the Control Module 8 Plug In Transformer A Plug Transformer into 120 VAC Receptacle...

Page 6: ...ime Out by configuring the number 1 2 and 3 Dip Switches as shown in Table 1 Table 1 Time Out Settings Unless otherwise specified all ETF 660 ETF 770 Faucets leave the factory set with a 30 second Time Out Note The position of Dip Switch 4 range enhancer setting does not affect Faucet Time Outs Push Cables into slots at the bottom of the Control Module Install Control Module cover using Screws pro...

Page 7: ...eering Department at 1 888 SLOAN 14 1 888 756 2614 OR 1 847 233 2016 Note Remove Cover from Control Module to check diagnostic lights 1 PROBLEM No water is delivered when Faucet is activated INDICATOR If no LED lights illuminate CAUSE No electricity is being supplied to Faucet SOLUTION Ensure that the main power is turned ON Check all Transformer Sensor Solenoid and Cable Connections Make sure tha...

Page 8: ...l Mixing Valve not shown Item Part Description No No OPTIONAL MIXING VALVES 13 MIX 60 A Below Deck Mechanical Water Mixing Valve BDM Variation 14 MIX 135 A Below Deck Thermostatic Water Mixing Valve BDT Variation 15 MIX 110 AA Optimix Deck Mounted Water Mixing Valve FAUCET CABLE EXTENSION CORDS Faucet to Control Module Solenoid to Control Module ETF 1005 26 26 0 7 meter Length ETF 1003 36 36 0 9 m...

Reviews: