9
TROUBLESHOOTING
1. Faucet does not function.
A. Adhesive packaging label affixed over sensor eye.
Remove adhesive label from sensor eye.
B. “Intermittent Off” is activated.
Press button once.
C. Water supply stop(s) closed.
Open water supply stop(s).
D. Battery is “dead”.
Replace battery (refer to Battery Replacement section of guide).
2. Faucet delivers water in an uncontrolled manner.
A. Reflection.
Remove reflective surface.
B. Faucet is not working properly.
Contact Sloan Valve Company Installation Engineering Department.
3. Faucet does not deliver any water when Sensor is activated.
Solenoid Valve produces an audible “CLICK.”
A. Water supply stop(s) closed.
Open water supply stop(s).
B. Water supply stop strainer(s) clogged.
Remove, clean, and reinstall water supply stop strainer(s). Replace
strainer(s), if required.
Solenoid Valve DOES NOT produce an audible “CLICK.”
A. Battery low (battery operated models).
Replace battery (refer to Battery Replacement section of guide).
B. Power failure.
Check power supply.
4. Faucet delivers only a slow flow or dribble when sensor is activated.
A. Water supply stop(s) are partially closed.
Completely open water supply stop(s).
B. Water supply stop strainer(s) clogged.
Remove, clean, and reinstall water supply stop strainer(s). Replace
strainer(s), if required.
C. Spray head is clogged.
Remove, clean, and reinstall spray head. Replace spray head,
if required.
D. Faucet is not working properly.
Contact Sloan Valve Company Installation Engineering Department.
5. Faucet does not stop delivering water or contrinues to drip after user is
no longer detected.
A. Faucet is not working properly.
Contact Sloan Valve Company Installation Engineering Department.
6. LED indicator blinks when faucet is in use.
A. Battery low (battery operated models).
Replace battery (refer to Battery Replacement section of guide).
7. The water temperature is too hot or too cold on a faucet connected to
hot and cold supply lines.
A. Supply stops are not adjusted properly.
Adjust supply stops.
When assistance is required, please contact Sloan’s
Installation Engineering Department at:
1-888-SLOAN-14 (1-888-756-2614)
CARE AND CLEANING
DO NOT USE
abrasive or chemical cleaners (including chlorine bleach) to
clean faucets that may dull the luster and attack the chrome or special
decorative finishes. Use
ONLY
mild soap and water, then wipe dry with
clean cloth or towel. While cleaning the bathroom sink, protect the faucet
from any splattering of cleaner. Acids and cleaning fluids will discolor or
remove chrome plating.
TECHNICAL DATA
NOMINAL VOLTAGE
POWER SUPPLY
WATER PRESSURE
FLOW RATE
WATER FLOW DURATION
WATER TEMPERATURE
6 VDC
120 VAC/ 6.75 VDC
4.3-125 PSI (0.3 - 8.6 bar)
1.5 gpm (5.7 Lpm)
0.5-4 seconds
MAx. 176°F/80°C