INSTALLATION 

 

 

Page 5 

 

  

Picture 1&10

 

To  facilitate  the  installation,  you  may  want  to  remove  the 
salt lid and main cover from the water softener. 
 

INLET & OUTLET 

 

 

Check the water pressure at the place of installation  of 

the water softener; it should never exceed 8,3 bar. 

 

 

In  case  of  high  concentration  of  impurities  in  the  inlet  

water, we recommend the installation of a sediment filter, 
ahead of the water softener. 

 

 

We  strongly  recommend  the  use  of  flexible  hoses  to 

connect  the  water  softener  to  the  water  distribution 
system;  use  hoses  with  a  large  diameter  in  order  to  limit 
the pressure loss. 

 

 

If  the  water  softener  is  not  equipped  with  the  factory 

bypass  (optional),  we  strongly  recommend  to  install  a  3-
valve  bypass  system  (not  included  with  this  product!)  to 
isolate  the  water  softener  from  the  water  distribution 
system in case of repairs. It allows to turn off the water to 
the  water  softener,  while  maintaining  (untreated)  water 
supply to the user. 

 

WITH FACTORY BYPASS (optional) 

 

  

Picture 2

 

 = mains water supply (untreated water) 

 = inlet of water softener (untreated water) 

 = outlet of water softener (treated water) 

 = house/application (treated water) 

 

1.

 

Screw the factory bypass onto the elbow connections of 
the  water  softener  (

&

);  make  sure  to  install  the 

gasket seals. Tighten the nuts firmly by hand. 

2.

 

Screw  the  connection  kit  with  nuts  onto  the  factory 
bypass  (

&

);  make  sure  to  install  the  gasket  seals. 

Tighten the nuts firmly by hand. 

3.

 

Connect  the  mains  water  supply  to  the  adaptor  on  the 
inlet port of the factory bypass (

). 

4.

 

Connect  the  house/application  to  the  adaptor  on  the 
outlet port of the factory bypass (

). 

 
WITH 3-VALVE BYPASS SYSTEM (not included) 

 

  

Picture 3

 

 = mains water supply (untreated water) 

 = inlet of water softener (untreated water) 

 = outlet of water softener (treated water) 

 = house/application (treated water) 

 
1.

 

Install the 3-valve bypass system. 

2.

 

Screw  the  connection  kit  with  nuts  onto  the  elbow 
connections of the water softener (

&

); make sure to 

install the gasket seals. Tighten the nuts firmly by hand. 

3.

 

Connect  the  3-valve  bypass  system  to  the  adaptors  on 
the in (

) and out (

) elbow connections. 

4.

 

Connect  the  mains  water  supply  to  the  inlet  of  the  3-
valve bypass system (

). 

5.

 

Connect  the  house/application  to  the  outlet  of  the  3-
valve bypass system (

). 

 

DRAIN

 

 

 

We recommend the use of a stand pipe with air trap.  

 

 

To prevent backflow from the sewerage system into the 

water  softener,  always  make  sure  to  have  an  air  gap 
between  the  end  of  the  drain  hose  and  the  sewerage 
system  itself;  as  a  rule  of  thumb,  the  air  gap  should  be 
minimum 2x the diameter of the drain hose. 

 

 

Always  use  separate  drain  hoses  for  the  control  valve 

(evacuation  of  rinse  water)  and  the  softener  cabinet's 
overflow. 

 

 

Lay-out the drain hoses in such a way that pressure loss 

is minimized; avoid kinks and unnecessary elevations. 

 

 

Make sure that the sewerage system is suitable for the 

rinse water flow rate of the water softener. 

 

  

Picture 4

 

1.

 

Connect  a  13  mm  hose  to  the  drain  solenoid  of  the 
control valve (

); secure it by means of a clamp. 

2.

 

Run the drain hose to the sewerage system and connect 
it to the stand pipe assuring sufficient air gap. This drain 
line  operates  under  pressure,  so  it  may  be  installed 
higher than the water softener. 

3.

 

Connect  a  13  mm  hose  to  the  cabinet  overflow  elbow, 
located at the back side of the water softener; secure it 
by means of a clamp. 

4.

 

Run the drain hose to the sewerage system and connect 
it to the stand pipe assuring sufficient air gap. This drain 
line does NOT operate under pressure, so it may NOT be 
installed higher than the water softener. 

 

ELECTRICAL 

 

  

Picture 5

 

1.

 

Plug the transformers output lead into the socket on the 
water  softeners  power  cord;  secure  it  by  means  of  the 
TwistLock clamp. 

2.

 

Plug the transformer into an electrical outlet. 

Summary of Contents for Eco 17L

Page 1: ...2013 Aquion Inc TM EN Slimline Rev2013 08 Technical Manual WATER SOFTENER...

Page 2: ...ow diagrams Eco Page 12 Hydraulic flow diagrams Eco Page 13 Troubleshooting Page 14 Electrical wiring diagrams Page 16 Default parameter settings Page 17 Exploded view Slimline 11L 14L Page 18 Explode...

Page 3: ...rtaken by a competent person aware of the local codes in force All plumbing and electrical connections must be done in accordance with local codes Before setting up the water softener make sure to che...

Page 4: ...oiler house or freezing temperatures can occur the water softener cannot be exposed to outdoor elements such as direct sunlight or atmospheric precipitation do not install the water softener too close...

Page 5: ...e application treated water 1 Install the 3 valve bypass system 2 Screw the connection kit with nuts onto the elbow connections of the water softener make sure to install the gasket seals Tighten the...

Page 6: ...show some discoloration close the tap 7 Check the water softener and all hydraulic connections for leaks After the first regenerations of the water softener some slight discoloration of the treated wa...

Page 7: ...the message In such case entering one of the programming levels can possibly solve the problem However if the problem persists professional service is required SERVICE MODE In service mode the display...

Page 8: ...scroll button the display will show Press the up or down button to set the language 2 Press the scroll button again the display will show Press the up or down button to set the time of day 3 Press th...

Page 9: ...aration Cycle 2 Cycle 2 Backwash Cycle 3 Brine draw slow rinse Cycle 3 Cycle 4 Fast rinse Cycle 5 7 Press the scroll button again the display will show Press the up or down button to set the type of w...

Page 10: ...e calculated volume of softened water between regenerations Hardness display shows the setting of the water hardness Rsrv display shows the setting of the reserve capacity Regen display shows the sett...

Page 11: ...rol valve and water conditioner salt The user should make sure that the brine cabinet is always kept full of water conditioner salt Therefore he should periodically check the salt level inside the bri...

Page 12: ...HYDRAULIC FLOW DIAGRAMS ECO Page 12 SERVICE REFILL BRINE PREPARATION BRINE DRAW SLOW RINSE...

Page 13: ...HYDRAULIC FLOW DIAGRAMS ECO Page 13 SERVICE REFILL BRINE PREPARATION BACKWASH BRINE DRAW SLOW RINSE FAST RINSE...

Page 14: ...fails to draw brine Improper refill time setting Verify that refill time corresponds to the proper salt level and amount of resin Missing refill flow control Verify that refill flow control is instal...

Page 15: ...or and or brine restrictor Clean injector and or brine restrictor Plugged injector filter Clean injector filter Restricted drain line Verify drain line for kinks or restrictions Restricted brine line...

Page 16: ...4VAC auxilliary contact closed during regeneration max 500mA refill solenoid white drain solenoid key pad ECO flow meter power lead 24VAC auxilliary contact closed during regeneration max 500mA refill...

Page 17: ...56 5 1 f M3 L equals 2 9 d M3 L 2 When the Exchange capacity per liter resin is changed the refill cycle time needs to be adjusted accordingly Model Eco Resin 11 17 24 Hardness unit 1 f f f Exchange...

Page 18: ...EXPLODED VIEW SLIMLINE 11L 14L Page 18...

Page 19: ...rine well 47 cm 14 38536 Screw rivet brine well 15 H1016 4 Brine well cap bottom 16 72263 Twist lock clamp power cord 17 28 298 11 Transformer 230 24V 50 Hz 24VA EuroT plug 18 70971 Power cord 19 7276...

Page 20: ...EXPLODED VIEW SLIMLINE 17L 24L 30L Page 20...

Page 21: ...rine valve assembly 464 to be cut to length 13 BW3 5 088 Brine well 14 38536 Screw rivet brine well 15 H1016 4 Brine well cap bottom 16 28 298 11 Transformer 230 24V 50 Hz 24VA EuroT plug 17 72263 Twi...

Page 22: ...EXPLODED VIEW VALVE BODY ASSEMBLY ECO Page 22...

Page 23: ...54 Spring clip 25 186 118 O ring brine plug 26 541 273 Brine plug 27 72467 Union gasket 2x 28 72542 Elbow inlet 29 19 19 Clip drain flow adjuster 30 186 134 O ring drain flow adjuster 2x 31 541 238 Dr...

Page 24: ...EXPLODED VIEW VALVE BODY ASSEMBLY ECO Page 24...

Page 25: ...1 254 Spring clip 25 186 118 O ring brine plug 26 541 273 Brine plug 27 72467 Union gasket 2x 28 72542 Elbow inlet 29 19 19 Clip drain flow adjuster 30 186 134 O ring drain flow adjuster 2x 31 541 238...

Page 26: ...2 72216 Valve head 3 541 300 G Drain flow control 2 0 gpm Eco 11L Eco 15L Eco 20L 541 300 J Drain flow control 2 6 gpm Eco 26L 4 185 115 1 O ring drain line adaptor 5 74018 Nut drain solenoid 6 74016...

Page 27: ...Page 27...

Page 28: ...vice flow rate 1 bar pressure drop m hr 2 3 2 3 2 1 1 9 2 0 Recommended maximum service flow rate m hr 3 1 1 1 4 1 7 2 4 3 0 Rinse water usage per regeneration Ltr 4 61 64 101 107 131 2 Indicative num...

Page 29: ...capacity per kg salt m x d 23 Service flow rate 1 bar pressure drop m hr 2 3 2 1 2 1 Recommended maximum service flow rate m hr 3 1 1 1 7 2 4 Rinse water usage per regeneration Ltr 4 110 139 175 2 Ind...

Page 30: ...Page 30...

Page 31: ...Page 31...

Page 32: ...AQUION INC Lammerdries Oost 30c B 2250 Olen Belgium 32 0 14 28 51 71 32 0 14 28 51 70 RPR RPM Turnhout BWT TVA VAT BE 0882 738 206 infobelgium eriewatertreatment com www eriewatertreatment com...

Page 33: ...2012 Aquion Inc PP SlimlineEco Rev2012 05 r 1 2 3 a 3 b...

Page 34: ...2012 Aquion Inc PP SlimlineEco Rev2012 05 r 4 a 4 b 5 a 5 b r 6...

Page 35: ...2012 Aquion Inc PP SlimlineEco Rev2012 05 r 7 8 a r 8 b r 8 c...

Page 36: ...2012 Aquion Inc PP SlimlineEco Rev2012 05 r 9 a 9 b 9 c r 10...

Reviews: