76
13 - USE
13.17 - “Installer’s
menu”
CAUTION!!!
Changing these
parameters could cause the
boiler and therefore the system
to malfunction. For this reason,
only a qualifi ed technician who
has in-depth knowledge of the
boiler should change them.
The boiler’s micro-processor makes
this menu of parameters available
to the
qualifi ed technician for the
analysis of the functioning and
adjustment of the appliance to the
system. When entering the “Installers’
Menu”, the display item “1” in Figure
13-1, will start to blink indicating that
a change of mode has taken place. To
access the “Installers’ Menu” just (see
also Section 17 to better understand
the several menus):
1. press and hold the
button
down for 12 seconds until the
parameter is displayed;
2. press and release the
button
to scroll through the list of the
parameters;
3. once the parameter has been
displayed, it can be changed using
the
or
keys;
4. press and release the
button
to confi rm the amended data before
moving to the next parameter.
When the last parameter has been
reached and the
button
pressed, the display will stop blinking
indicating the exit from the menu.
NOTE: If no key is pressed for
more than 60 seconds, the control
automatically exits the “Installers’
menu”. Any parameter change not
saved using the
button, will be
lost.
The next table lists each “Installers’
menu” parameter, what it affects and
its adjustment range.
PARAMETER DESCRIPTION
INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed) (displayed only if outdoor reset is
active, as per section 13.9)
Value from 0 to 99 (cannot be changed)
(30 corresponds to a current of 1uA)
(99 corresponds to a current of 5.5 uA)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Value in °F (cannot be changed)
Can be changed in accordance with Section 11.6
00 = contact open (heating service off)
01 = contact closed (heating service on)
Value in g/1’/100 (rpm/100) (cannot be changed)
Adjustable according to the instructions of section 12.10
Boiler temperature, measured by U1
sensor
DHW temperature, measured by U2
sensor
Domestic cold water (or ind. water heater)
temperature , measured by U3 sensor
Outdoor temperature, measured by U4
sensor
Ionization current value
High limit temperature, measured by U6
sensor
Flue gas temperature, measured by U7
sensor
Heating return temperature, measured
by U8 sensor
Type of basic setting of control board
Status of room thermostat contact
Measurement of fan speed rotation
BTU input for heating service
Continue