10 - INSTALLATION - Vent and combustion air
10.9.3 - Polypropylene
concentric system
The boiler is not supplied with the
fi ttings needed for connecting a
coaxial vent/combustion air system.
A special kit must be ordered to
connect the boiler with the Coaxial
polypropylene vent. Figure 10-14
shows how to install the Coaxial fi tting
above the boiler. Tight the screws “D”
of Figure 10-14 with a tork of 2 lbf ft
(3 Nm)
WARNING!!!
Carefully
follow installation steps below,
for the coaxial pipe assembly
(elbows and extensions), as
illustrated in Figure 10-15. It is
necessary to properly insert
the internal and external pipe
and mechanically secure them
by using a stainless steel
self tapping screw. Improper
venting can result in excessive
levels of carbon monoxide or a
fi re, which can result in severe
personal injury or death!
In particular:
1. slip-fi t the extension “1” and “2”
(see Figure 10-15) together;
2. drill a suitable hole “3” with a drill
“4” (see Figure 10-15) in a position
where the two pipes “1” and “2” are
overlapped;
3. insert a suitable stainless steel self
tapping screw “5” and tight it with a
screwdriver “6”
It is recommended that wall sleeve
be used when installing the coaxial
system through an exterior wall.
This will allow the system to be
easily slipped out for access during
routine maintenance.
Horizontal coaxial systems must
always be pitched by at least 1/4 in/
ft,
(21 mm/m)
towards the boiler.
Figure 10-14 Installation of the coaxial fi tting
Figure 10-15 Securing extensions and elbows together
B = Connection fl ange
C = Fasten clip
D = Fasten clip screw
F = Coaxial vertical adaptor