10
SKYBLADe FANS
-
Where Form Follows Function
5
MoUNTiNg MeThoD 1
:
UNi
-
STRUT
5.1 Select Proper Unistrut:
NOTE:
Unistrut and Unistrut hardware is not included with the fan. This equipment must be field
supplied.
Do not install the fan from a single purlin, truss, or bar joist.
Ne pas installer le ventilateur à partir d’une seule panne, botte, ou solives.
Unsupported unistrut spans should not exceed 12’ (3.7m).
Non pris en charge travées de fer d’angle ne doit pas dépasser 12 pi (3,7 m).
Do not install motor and hub assembly directly on unistrut.
Ne pas installer moteur et moyeu directement sur cornière.
Follow the table below when selecting Unistrut for fan installation. PLEASE NOTE: These are suggestions.
SkyBlade is not liable for accidents resulting from improperly sized mounting methods. Please consult
a structural engineer.
Unistrut Span
(between
mounting
point)
Minimum
Unistrut Size
(W x H x T)
Qty. of
Unistrut
Needed
< 8’ (2.4m)
1-5/8”
2
Support Directly From Building Structure.
All mounting instructions assume that the building structure from which the fan will be
hung is of sound construction, undamaged, and capable of supporting loads of up to
650 lbs (295 kg). It is the sole responsibility of the customer to verify that the building’s
structure is adequate for fan installation. Skyblade Fans recommends consulting with a
structural engineer prior to fan installation.
Aider directement à la structure du bâtiment.
Toutes les instructions de montage supposent que la structure du bâtiment à partir de laquelle le
ventilateur sera pendu est de construction solide, en bon état, et capable de supporter des charges
de jusqu’à 650 lb (295 kg). Il est de la seule responsabilité du client de vérifier que la structure du
bâtiment est suffisante pour l’installation du ventilateur. Skyblade fans recommande de consulter un
ingénieur en structure avant d’attiser installation.
WARNING/ AVERTISSEMENT
!