DOL 634 CE
Technical User Guide
43
Select the function to be tested and test the components one at
a time.
A colored bar at the top of the page indicates that a component
is set for manual mode.
After testing the components, you must set the function back to automatic control, so that the house
controller continues to operate as before.
I/O will remain in the setting that it was on at the moment the component was set to manual. This means that
operation continues when it is returned to automatic control.
12.2.1 Testing Climate Functions
12.2.1.1 Testing the central air intake
Select the menu
Technical | Manual/auto | Central air intake and
activate
Manual
.
Testing Heating
The test should indicate if it is possible for the system to be started and stopped.
Select
Heating
and set to 0% to check that the heat source stops.
Select
Heating
and set to 100% to check that the heat source provides constant heating.
Testing cooling relay
The test should indicate if it is possible for the system to be started and stopped.
Activate the
Cooling relay
.
Check that the system (cooling) is on.
Deactivate the
Cooling relay
.
Check that the system (cooling) is off.
Testing air inlets
The test is to show whether the air inlets can open and close completely.
Set 100 %.
Check that the correct air inlet opens completely.
Set 0 %.
Check that the correct air inlet closes completely
Set the air inlet to the required setting.
Repeat the test for all installed air inlets.
12.2.1.2 Testing of central exhaust
12.2.1.2.1 Stepless fans
Testing setting and placement of stepless fans